COOK ETS User Manual

Rebel/aq/sep/ete/ets, Installation, operation, and maintenance manual

Advertising
background image

Propeller Roof Fans

INSTALLATION, OPERATION, AND MAINTENANCE MANUAL

REBEL/AQ/SEP/ETE/ETS

This publication contains the installation, operation

and maintenance procedures for standard units of the
REBEL/AQ/SEP/ETE/ETS - Propeller Roof Fans.

Carefully read this publication prior to any installa-

tion or maintenance procedure.

Loren Cook catalog, Propeller Roof Fans, provides addi-

tional information describing the equipment, fan perfor-
mance, available accessories and specification data.

For additional safety information, refer to AMCA publica-

tion 410-96, Safety Practices for Users and Installers of
Industrial and Commercial Fans
.

All of the publications listed above can be obtained from

Loren Cook Company by phoning (417)869-6474, exten-
sion 166; by FAX at (417)832-9431; or by e-mail at
[email protected].

For information and instructions on special equipment,

contact Loren Cook Company at (417)869-6474.

Receiving and Inspection

Carefully inspect the fan and accessories for any dam-

age and shortage immediately upon receipt of the fan.

• Turn the propeller by hand to ensure it turns freely and

does not bind.

• Check dampers (if included) for free operation of all

moving parts.

• Record on the Delivery Receipt any visible sign of

damage.

Handling

Lift the fan by the base or by the shipping carton. Never

lift by the shaft, motor or housing.

If your fan is covered with a protective coating (e.g., phe-

nolic enamels, or other protective coatings), handle with
extreme care
. Even a small chip will break the coating’s
continuity and destroy its ability to protect the metal.

Propellers are carefully balanced to give smooth, vibra-

tion-free operation. If the propeller is damaged during han-
dling, it will require rebalancing.

Storage

If the fan is stored for any length of time prior to installa-

tion, store it in its original shipping crate and protect it from
dust, debris and the weather.

Outdoor Storage

WARNING

This unit has rotating parts. Safety precautions

should be exercised at all times during installation,
operation, and maintenance.
ALWAYS disconnect power prior to working on fan.

REBEL/AQD/SEP

To maintain good working condition of the fan when it is

stored outdoors or at a construction site, follow the addi-
tional instructions below.

• Coat the shaft and bearings with grease or rust preven-

tative compound to help seal out moisture.

• Periodically rotate the propeller and operate the damp-

ers (if supplied) to keep a coating of grease on all inter-
nal bearing parts.

• Periodically inspect the fan to prevent damaging condi-

tions.

• Block propeller to prevent natural rotation.
• Cover the unit with some type of weather cover to pre-

vent moisture, corrosion, dirt or dust accumulation.

Installation

Damper Installation

If your fan is supplied with dampers, follow the directions

below. If your fan does not include dampers, proceed to
Motor Installation.

a. Place the damper inside the curb. Ensure the damper

will open freely for the correct direction of the airflow.

b. Secure to curb at the damper shelf by installing at least

two sheet metal screws (#10 x 1/2”) on each side of the
damper, through the tray, with the screw head catching
the flange on the damper. This will prevent the exhaust
dampers from lifting and keep the supply dampers cen-
tered.

c. Drill a hole in the curb shelf for conduit needed for

motor wiring.

Personal Safety

Disconnect switches are recommended. Place

the disconnect switch near the fan in order that
the power can be swiftly cut off in case of an
emergency, and in order that maintenance per-
sonnel are provided complete control of the
power source.

Advertising
This manual is related to the following products:
Table of contents