Installation, Installation, operation, and maintenance manual, Receiving and inspection

Advertising
background image

Storage

If the fan is stored for any length

of time prior to installation, store it
in its original shipping crate and
protect it from dust, debris and the
weather.

Installation

If the fan was delivered with the

motor unmounted, see the mainte-
nance sections for belt and pulley
installation.

If the fan was purchased as a wall

mount unit and a grease terminator or grease trough was
not purchased, a 1-1/16 inch diameter drain hole should be
inserted on the bottom side of the unit for drainage.

Fan Installation

a. Ensure the fan discharge is a minimum 40 inches

above the roof surface and a minimum of 10 foot from any
building air intake in order to comply with NFPA 96.

The attachment of roof mounted fans to the roof curb
as well as the attachment of roof curbs to the building
structure must exceed the structural requirements
based on the environmental loading derived from the
applicable building code for the site. The local code
official may require variations from the recognized
code based on local data. The licensed engineer of
record will be responsible for prescribing the correct
attachment based on construction materials, code
requirements and environmental effects specific to
the installation.

Failure to follow these instructions could result in
death or serious injury.

Centrifugal Roof and Wall Exhausters

INSTALLATION, OPERATION, AND MAINTENANCE MANUAL

This publication contains the installation, operation and
maintenance procedures for standard units of the VCR,
VCRD, VCR-HP, VCRD-HP, VCR-XP, & VCRD-XP
Centrifugal Roof and Wall Exhausters
.

Carefully read this publication and any
supplemental documents prior to any
installation or maintenance procedure.

Loren Cook Company’s VCR catalog provides addi-

tional information describing the equipment, fan perfor-
mance, available accessories and specification data.

For additional safety information, refer to AMCA publica-

tion 410-96, Safety Practices for Users and Installers of
Industrial and Commercial Fans
.

All of the publications listed above can be obtained from

Loren Cook Company by phoning (417)869-6474, exten-
sion 166; by FAX at (417)832-9431; or by e-mail at
[email protected].

For information on special equipment, contact Loren

Cook Company Customer Service Department at
(417)869-6474.

Receiving and Inspection

Immediately upon receipt of a VCR fan, carefully inspect

the fan and accessories for damage and shortage.

• Turn the wheel by hand to ensure it turns freely and

does not bind.

• Record on the Delivery Receipt any visible sign of

damage.

Handling

Lift the fan by the lifting lugs provided under top cap.

NOTICE! Never lift by the shaft, motor or housing.

Rotating Parts & Electrical Shock Hazard:

Disconnect electric power before working on unit.

Follow proper lockout / tagout procedures to ensure
the unit cannot be energized while being installed or
serviced.

A disconnect switch should be placed near the fan
in order that the power can be swiftly cut off, in case
of an emergency and in order that maintenance
personnel are provided complete control of the
power source.

Grounding is required. All field-installed wiring must
be completed by qualified personnel. All field-
installed wiring must comply with National Electric
Code (NFPA 70) and all applicable local codes.

Failure to follow these instructions could result in
death or serious injury.

VCR

Lifting Lugs