Nor-Lake Undercounter & Freestanding Refrigerators User Manual

Nor-Lake Refrigerators

Advertising
background image

UNDERCOUNTER & FREESTANDING

REFRIGERATOR

Installation, Operation and

Maintenance Instructions


INSPECTION



When the equipment is received, all items should be carefully checked against the bill of lading to
insure all crates and cartons have been received. All units should be inspected for concealed
damage by uncrating the units immediately. If any damage is found, it should be reported to the
carrier at once, and a claim should be filed with the carrier. This equipment has been inspected and
tested at the manufacturing facility and has been crated in accordance with transportation rules and
guidelines. Manufacturer is not responsible for freight loss or damage.

Before connecting the refrigerator to the power supply, let it stand for approximately two hours to
reduce the possibility of malfunctions in the cooling system due to transport handling

INSTALLATION

GENERAL


After the unit crate and crate base have been removed, place the refrigerator firmly on a solid base.
Adjust the adjustable feet on the front of the cabinet to level the refrigerator (see Figure 1). The
ventilation grid may be placed close to a wall as the grid allows for sufficient air circulation required
for adequate ventilation (see Figure 2). For total enclosure, allow 2 inches of clearance all around
for ventilation.







Figure 1

Figure 2

ELECTRICAL


Check the proposed outlet to be used to insure that the voltage, phase, and current carrying
capacity of the circuit from the electrical panel correspond to the requirements of the cabinet.
NEVER use an extension cord to wire any unit. Refer to the serial tag for all pertinent electrical
information.

Observe all Warning Labels. Disconnect power supply to eliminate injury from electrical
shock or moving parts when servicing equipment.

1

9/09 133288

Advertising