General, Inspection, Location – Nor-Lake Large Capacity Incubator User Manual

Page 2: Installation

Advertising
background image

GENERAL

INSPECTION

When the equipment is received, all items should be carefully checked against the bill of lading to
insure all crates and cartons have been received. All units should be inspected for concealed
damage by uncrating the units immediately. If any damage is found, it should be reported to the
carrier at once, and a claim should be filed with the carrier. This equipment has been inspected and
tested in the manufacturing facility and has been crated in accordance with transportation rules and
guidelines. Manufacturer is not responsible for freight loss or damage.

LOCATION

The cabinet should also be leveled when it is placed in its permanent location. Do not stack items
on top of the unit. Vibration during shipping and handling may loosen mechanical connections.
Check all connections during installation. Check all wiring and fasteners.

CAUTION

• Do not modify cabinet construction or associated equipment assemblies.

• Do not remove labeling or information supplied with the unit.

Observe all Warning Labels. Disconnect power supply to eliminate injury from electrical
shock or moving parts when servicing equipment.

INSTALLATION

Door Alignment - If for some reason the doors are not squared up on the cabinet, the doors can be
adjusted. Opening the door(s) and loosening the screws that hold both the top and bottom hinges to
the cabinet can accomplish this. After adjusting the door so that it is aligned correctly, tighten the
screws to securely hold the hinges in place.

Shelving Installation - Locate shelves inside cabinet, install shelf supports (1 RH
support, 1 LH support per shelf.)

Remote Alarms Contacts Access
- The factory installed Remote alarm contacts
access box is located at the top of the cabinet behind the microprocessor control
(see illustration.)

1. Remove the cover to access the terminal

connections.

2

7/10 Rev. C 131783

2. Select and knock-out a hole to run field leads

into electrical box terminals.

3. The terminal block in the electrical box is

labeled for “normally open” and “normally
closed” activation. End user is responsible for
proper field installation.

Terminal connections are rated for class II
circuits only per NEC table 11(A). (Limited
power source less than 30vac 8 Amp. max, see
applicable notes in NEC).

2-10 volt DC Output – Terminal board for 2-10v DC
Output for temperature re-transmit is located behind
the cabinet façade, next to Remote Alarm access box. Connect wires as per label.

Advertising