American Electric Lighting DTD User Manual

Installation instructions dtd series luminaire, Warning, Caution

Advertising
background image

INSTALLATION INSTRUCTIONS

DTD SERIES LUMINAIRE

American Electric Lighting a division of Acuity Lighting Group, Inc. Conyers, GA

DRAWING NO. A67570 REV A

©2007 ACUITY LIGHTING GROUP, INC.

PART NUMBER 057-71-67570

WARNING

DISCONNECT POWER BEFORE RELAMPING OR WIRING THE FIXTURE.

READ ALL INSTRUCTIONS COMPLETELY BEFORE STARTING INSTALLATION

TO AVOID THE RISK OF FIRE OR SHOCK, FIXTURE MUST BE INSTALLED IN COMPLIANCE WITH ALL APPLICABLE NATIONAL

AND LOCAL ELECTRICAL/BUILDING CODES. FOR CODE INTERPRETATION, CONSULT LOCAL CODE AUTHORITY.

CHECK THAT INPUT VOLTAGE IS THE SAME AS LUMINAIRE VOLTAGE STATED ON THE BALLAST LABELS OR LEADS

CAUTION

!

!

FIG. 1

11/16" DIA.

HOLE

36"

16"

12"

FIG. 2

TO PREVENT DAMAGE TO ALUMINUM HOUSING, DO NOT OVERTIGHTEN UPPER THROUGH BOLT.

CAUTION

!

IT IS NOT NECESSARY TO REMOVE THE COVER FOR MOUNTING. THE LAMP AND PHOTO-CONTROL SHOULD BE

ASSEMBLED ON THE GROUND. ADJUST THE PHOTO-CONTROL TO ORIENT NORTH LIFT AND ROTATE THE RECEPTACLE SO THAT THE

ARROW ON THE TOP POINTS NORTH. RELEASE THE RECEPTACLE. PLUG THE PHOTOCONTROL INTO THE RECEPTACLE AND TWIST IT

CLOCKWISE UNTIL IT LOCKS INTO POSITION.

MOUNTING ON WOOD POLES (SEE FIG. 1)

1. LOOSELY ASSEMBLE THE 5/8" x 10" BOLT IN POLE.

2. HANG THE BRACKET ARM OVER THE HEAD OF THE THROUGH BOLT IN THE POLE. ALIGN THE UNIT VERTICALLY AND TIGHTEN

THE NUT (RETAINING LUGS INSIDE THE ARM PREVENT THE THROUGH BOLT FROM TURNING).

3. DRIVE IN THE LAG SCREW AND TIGHTEN

4. CONNECT THE SUPPLY WIRES AND GROUND WIRE AND CHECK THE LUMINAIRE IS OPERATING CORRECTLY BY COVERING THE

PHOTO-CONTROL TEMPORARILY.

SUGGESTIONS FOR MOUNTING ON OTHER THAN WOOD POLES

ROUND POLES (STEEL, ALUMINUM OR CONCRETE)

BACK PLATE WILL SEAT ON ROUND POLES TO A MINIMUM 3 1/2" DIAMETER. THE BRACKET ARM MAY BE ATTACHED BY 2

STAINLESS STEEL CLAMP BANDS ASSEMBLED THROUGH SLOTS IN BRACKET ARM.

FLAT WALLS

BACK PLATE WILL ALSO SEAT ON FLAT WALLS WHERE A THROUGH HOLE CAN BE CREATED

(SEE FIG. 2 FOR HOLE LOCATIONS AND DIMENSIONS)

5"

7/16" DIA.

HOLE

5/8" x 10" BOLT

3/8" x 3"

LAG SCREW

IF LAMP IS MARKED IT CONTAINS MERCURY. FOLLOW DISPOSAL LAWS. SEE WWW.LAMPRECYCLE.ORG

Hg

Advertising