6 additional installation tips, 1 grounding the panel pc, Grounding the panel pc – Beijer Electronics EPC TA150 AM EN User Manual

Page 15: 6additional installation tips

Advertising
background image

Additional Installation Tips

6

Additional Installation Tips

When experiencing communication problems in for example noisy environments
or when operating close to temperature limits, the following recommendations
are to be noticed.

6.1 Grounding the Panel PC

1

2

3

4

5

6

Door

Panel PC

Ferrite core

Mounting plate in the cabinet

Power supply

24 V DC

5350

The Panel PC’s mounting clamps do not provide a secure grounding connection
between the Panel PC and the device cabinet, see 1 in drawing above.
1. Connect a 2.5 mm

2

wire between the Panel PC’s quick-connect plinth and the

panel chassis, see 2 in drawing above.

2. Connect a 6 or 4 mm

2

wire or grounding braid between the panel’s chassis and

the closest grounding point on the door, see 3 in drawing above.

3. Connect a strong but short grounding braid between the door and the device

cabinet, see 4 in drawing above.

4. Twist the cables onto the 24 V DC feed, see 5 in drawing above.

2 turns around the ferrite core provide 4 times the suppression of 1 turn.
3 turns around the ferrite core provide 9 times the suppression of 1 turn.

A ferrite core suppresses disturbances to the 24 V feed, see 6 in drawing above.

Note:
The grounding wires should be short and the conductor should have a large area.
A long, thin grounding wire has a very high impedance (resistance) at high frequencies
and will not guide disturbances to the ground.
Multi-wire conductors are better than single wire conductors with the same area.
A braided conductor wire with the same area is even better. The best is a short, thick
grounding braid.

Beijer Electronics, MAEN041

15

Advertising