Fnio s-series, Na-9379, Quick guide – Beijer Electronics NA-9379 User Manual

Page 5: Fieldbus input/output system

Advertising
background image

FieldBus Input/Output System

MODBUS Programmable I/O

PROFIBUS Network Adapter

Digital Input / Output

Analog Input / Output

Special Module

Quick Guide

FnIO S-series

1. NA-9379 Specification

Class 2, adjacent to voltage rating (30Vmax.)

ITEM

SPECIFICATION

ITEM

SPECIFICATION

Operating/Storage Temp.

-20℃~60℃ / -40℃~85℃

Network Type

Modbus/TCP

Relative Humidity

5% ~ 90% Non-Condensing

Cable

Ethernet Cable(Shield Cable)

Durable-vib./impact

IEC68-2-6(2G) / 10G

Cable Length(m)

Up to 100m from Ethernet Hub

EMC/ESD

EN 61000-6-2:2005

EN 61000-6-4/A11:2011

Max. In/Output Size

/Comm. Sp(Kbps)

126Words / 126Words

10/100Mbps

Mount Position

On the left of FnIO-S series

Expansion No.

Max. 32 Modules

Atmosphere

Not so dusty without corrosive gas Interface Connector

RJ-45 Socket 2pcs

Field Supp. Volt.

Class 2, 24VDC

24VDC (11VDC ~ 28.8VDC)‏

Programming

/

Program Languages

CoDeSys V3.5 SP3 Patch 1

/IEC 61131-3 (LD, IL, ST, FBD, SFC)

Field Supp. Cur.

Max. 10A

Program Memory

512Kbytes

FnBus Sup. Cur

Max. 1.5A@5Vdc

Data Memory

512Kbytes

Isolation

System power to internal logic :

Non-isolation

System power to I/O driver :

Isolation

Non-Volatile

Memory

32Kbytes

(Retain : 16Kbytes, Flag : 16Kbytes)

Size

54mm × 99mm × 70mm

Max. nodes

Limited by Ethernet Specification

Protocol

MODBUS/TCP, DHCP

BOOTP, SNMP

Configuration

Port(RS232/485)

Node: 1 / Baud rate: 38400 / Data bit: 8

/Parity bit: No parity / Stop bit: 1

Weight

167g

Certification

UL/CE

Cautions for your Safety

 Do not assemble the products and wire with power applied to the system. Else it may cause an electric arc, which can result into unexpected

and potentially dangerous action by field devices. Arching is explosion risk in hazardous locations. Be sure that the area is non-hazardous or
remove system power appropriately before assembling or wiring the modules.

 Do not touch any terminal blocks or IO modules when system is running. Else it may cause the unit to an electric shock or malfunction.
 Keep away from the strange metallic materials not related to the unit and wiring works should be controlled by the electric expert engineer.

Else it may cause the unit to a fire, electric shock or malfunction.

If you don’t follow the directions, it could cause a personal injury, damage to the equipment or explosion

If you disobey the instructions, there may be possibility of personal injury, damage to equipment or
explosion. Please follow below Instructions.

 Check the rated voltage and terminal array before wiring. Avoid the circumstances over 60℃ of temperature. Avoid placing it directly in the
sunlight.
 Avoid the place under circumstances over 90% of humidity.
 Do not place Modules near by the inflammable material. Else it may cause a fire.
 Do not permit any vibration approaching it directly.
 Go through module specification carefully, ensure inputs, output connections are made with the specifications. Use standard cables for wiring.
 Use Product under pollution degree 2 environment.

Before using the unit

*We appreciate you for purchasing CREVIS Products. To use the units more effectively, please read this quick guide and refer to
the respective user manual for further details.

Warning!

Caution!

* Power Isolators must be used according to the usage of 5VDC/24VDC/48VDC or AC Voltage modules

NA-9379

Rev 1.00

Update date : 2014.06.13