Smart-UPS RT 15000/20000 VA 230 Vac Stack/Rack-Mount 6U User Manual

Specifications

Environmental Specifications

Physical Specifications

Temperature

Operating

Storage

32

°

to 104

°

F (0

°

to 40

°

C)

5

°

to 113

°

F (-15

°

to 45

°

C) charge the UPS battery every

six months
86

°

to 158

°

F (30

°

to 70

°

C) charge the UPS battery every

three months

This unit is intended for indoor use only.

Select a location sturdy enough to handle

the weight.
Do not operate the UPS where there is

excessive dust or the temperature or

humidity are outside the specified limits.
This unit has front to rear airflow. Allow

adequate space for proper ventilation.
Environmental factors impact battery life.

High temperatures, poor utility power, and

frequent, short duration discharges will

shorten battery life.

Maximum

Elevation

Operating

Storage

10,000 ft (3,000 m)

50,000 ft (15,240 m)

Humidity

0 to 95% relative humidity, non-condensing

Weight (unpacked)

UPS

145 lbs (66 kg)

XL Battery Pack

with eight battery

modules

400 lbs (181 kg)

Each battery

module

38 lbs (17 kg)

Maximum Number of XLBPs Supported by the Smart-UPS XL

10

Dimensions

773 mm
30.4 in

432 mm
17 in

26

3 m

m

10

.4

in

10

2

m

m

4 in

482 mm
19 in

465 mm

18.3 in