Specifications, Warranty – NOVUS DigiRail-2A User Manual

Page 2

Advertising
background image

DigiRail-2A

NOVUS AUTOMATION

2/2

SPECIFICATIONS

Inputs: 2 universal analog inputs.

Input signals: Configurable. Refer to Table 1.

Thermocouples: Types J, K, T, R, S, B, N and E, according to
NBR 12771. Impedance >> 1M

Pt100: 3 wires type,

α

= .00385, NBR 13773, Excitation of 700

µ

A.

For using Pt100 2 wires, interconnect terminals 2 and 3.

When gauging the module using the calibrator for
Pt100, be sure that the minimum current required for
it is compatible with the specified excitation current:
700

µ

A.

Other Signals:

0 to 20 mV, -10 to 20 mV, 0 to 50 mV.
Impedance >> 1 M

0 to 5 Vdc, 0 to 10 Vdc. Impedance >> 1 M

0 to 20 mA, 4 to 20 mA.
Impedance = 100

(+ 1.7 Vdc)

Overall accuracy (at 25°C): Thermocouples: 0.25% of the
maximum range,

±

1°C; Pt100, voltage and current: 0.15% of the

maximum range;

Input Signal

Maximum Measuring Range

Thermocouple J

-130 to 940 °C (-202 to 1724 ºF)

Thermocouple K

-200 to 1370 °C (-328 to 2498 ºF)

Thermocouple T

-200 to 400 °C (-328 to 752 ºF)

Thermocouple E

-100 to 720 °C (-148 to 1328 ºF)

Thermocouple N

-200 to 1,300 °C (-328 to 2372 ºF)

Thermocouple R

0 to 1760 °C (-32 to 3200 ºF)

Thermocouple S

0 to 1760 °C (-32 to 3200 ºF)

Thermocouple B

500 to 1800 °C (932 to 3272 ºF)

Pt100

-200 to 650°C (-328 to 1202 ºF)

0 to 20 mV

-10 to 20 mV

0 to 50 mV

* 0 to 5 Vdc

Adjustable between -31000 and +31000

* 0 to 10 Vdc

0 to 20 mA

4 to 20 mA

Table 1 – Sensors and signals accepted by the module

Sampling rate: from 2.5 to 10 samples per second

Internal compensation of cold junction for thermocouples

Power: 10 to 35 Vdc / 50 mA maximum. Internal protection against
polarity inversion.

Electrical insulation between inputs and supply/serial port:
1000 Vac

Serial communication: RS485 at two wires, Modbus RTU protocol.
Configurable parameters: Communication speed: from 1200 to
115200 bps; Parity: even, odd or none

Key for restoring communication parameters: The RCom key, at
the front panel, will set the device in diagnostics mode (address
246, baud rate 1200, parity even, 1 stop bit), able to be detected
and configured by the DigiConfig software.

Frontal light indicators for communication and status:

TX:

Signalizes that the device is sending data on the

RS485 line;
RX:

Signalizes that the device is receiving data on the

RS485 line;

Status:

When the light is permanently on, this means that

the device is in normal operation; when the light is flashing in a
second interval (approximately), this means that the device is in
diagnostics mode; when the light is flashing fast, this means
that there is an internal error.

Electromagnetic compatibility: EN 61326:2000

Operating temperature: 0 to 70 °C

Operational relative humidity: 0 to 90% RH

Envelope of the terminals: Polyamide

Assembly: DIN 35 mm rail

Dimensions: Refer to Figure 3.

Figure 3 – Dimensions