Rate, T sp, Atvn – NOVUS Controller N480 User Manual

Page 2: Kyst, A1sp, A2sp, Type, Vnit, Spll, Spkl

Advertising
background image

Controller N480

Novus Produtos Eletrônicos Ltda.

Tel.:+55-51-3323-3600

2/3

After the last parameter in one level is reached the controller returns
to operation level and the display will indicate the measured
temperature.
The display will also go back to the measured temperature whenever
the display is inactive for 20 seconds or more.
When a parameter value is changed via keyboard the controller will
only accept the new value after the user presses the INDEX key to
go to next prompt or if the keyboard is left inactive for 20 seconds.

For disabling the keyboard, move the internal strap to the position
KEY DISABLE. All parameters will be protected, accept the SP
parameter
.

KEY
DISABLE

KEY
DISABLE

Figure 2 – Strap in normal operating

position (enabled)

Figura 3 – Strap position for inhibiting the

keyboard

3.2. OPERATION

LEVEL

TEMPERATURE

INDICATION

END

SP

Set Point

TEMPERATURE measured by the sensor.
At power up, the upper display shows the process
temperature value. It also shows the messages
described in chapter 5 of this manual.
The lower displays shows the set point value which
is the temperature value desired for the process.

rAte

rAtE

TEMPERATURE RATE OF RISE: The user defines
the rate of temperature rise from the starting
temperature to the value set in “ SP

SP

SP

SP

”.

Rate is defined in °C / minute.

T Sp

time for soak

TIME FOR SOAK: Time in minutes which the
temperature will remain at the selected “ SP

SP

SP

SP

“.

Refer to item 4.

Rvn

run

RUN: At this prompt the user sets the control output
and alarms to active or to inactive.
0

0

0

0

- inactive outputs; 1

1

1

1

- active outputs;

3.3. TUNING AND ALARMS LEVEL

Atvn

Auto tune

AUTO-TUNE: Activates the auto-tuning of PID
parameters.
0

0

0

0

- Auto-tune is off;

1

1

1

1

- Auto-tune is on;

Pb

Proportional

band

PROPORTIONAL BAND: percentage of maximum
input span.

When set ot zero (0), control action is ON/OFF.

Ir

integral rate

INTEGRAL RATE: Integral time constant in
repetitions per minute (Reset). This constant is not
used when controller is set to ON/OFF action
(Pb=0).

Dt

derivative

time

DERIVATIVE TIME: Derivative time constant in
seconds. This constant is not used when controller
is set to ON/OFF action (Pb=0).

(t

Cycle time

CYCLE TIME: Pulse Width Modulation (PWM)
period in seconds. This term is not used when
controller is set to ON/OFF action (Pb=0).

KySt

HYSterisis

CONTROL HYSTERESIS: Is the hysteresis for
ON/OFF control (set in temperature units).
This parameter is only used when the controller is
in ON/OFF mode (Pb=0).

A1SP

SP Alarm 1

SETPOINT for Alarm 1: Triping point for alarm 1

A2SP

SP Alarm 2

SETPOINT for Alarm 2: Triping point for alarm 2

3.4. CONFIGURATION LEVEL

Type

tYPE

INPUT TYPE: Selects the input sensor type to be
connected to the controller. This is the first
parameter to be set.
0

0

0

0

- Thermocouple type J;

1

1

1

1

- Thermocouple type K;

2

2

2

2

- Thermocouple type S;

3

3

3

3

- Pt100 with 0,1° resolution;

4

4

4

4

- Pt100 with resolution;

5

5

5

5

- Thermocouple type T;

6

6

6

6

- Thermocouple type E;

7

7

7

7

- Termopar tipo N;

8

8

8

8

- Termopar tipo R;

Vnit

unit

TEMPERATURE UNIT: Selects display indication
for degrees Celsius or Farenheit.
0

0

0

0

- degrees Celsius ( °C );

1

1

1

1

- degrees Farenheit ( °F );

A(t

ACtion

CONTROL ACTION:
0

0

0

0

- reverse action. Generally used for heating.

1

1

1

1

- direct action. Generally used for cooling.

(ntr

Control

CONTROL OUTPUT:
0

0

0

0

- Sets control output to terminals OUT A.

1

1

1

1

- Sets control output to terminals OUT B.

As control output is defined to terminals OUT A,
alarm output is automatically set to OUT B.
If control output is defined to OUT B alarm 1 will
then be automatically set to OUT A.

spll

SP Low Limit

SET POINT LOW LIMIT: sets the lower range for
SV

spKl

SP High Limit

SET POINT HIGH LIMIT: Sets the upper range for SV.

A1fv

Alarm 1 Function

FUNCTION OF ALARM 1: Refer to table 2 for
function description and respective codes to set at
this prompt.

A2fv

Alarm 2 Function

FUNCTION OF ALARM 2: Refer to table 2 for
function description and respective codes to set at
this prompt.

Aiky
A2ky

Alarm HYsteresis

ALARM 1 AND ALARM 2 HYSTERESIS: Defines
the differential range between the PV value at
which the alarm is turned on and the value at which
it is turned off (in engineering units).

3.5. CALIBRATION

LEVEL

A T E N T I O N

These parameters are used to calibrate the temperature
measurement and should only be dealt with by experienced and well
equipped personnel.

Inl(

Input Low

Calibration

SENSOR OFFSET CALIBRATION. Sets the
temperature sensor low calibration (offset). The
display shows only the corrected temperature and
not the offset added. A signal simulator should be
used to inject a low value signal to properly adjust
the offset.

InK(

Input High

Calibration

INPUT HIGH CALIBRATION. Sets the sensor input
circuit gain or high calibration.
A signal simulator should be used to inject a high
value signal to properly adjust the offset.

(j L

Cold Junction Low

Calibration

COLD JUNCTION OFFSET CALIBRATION: Sets
the cold junction offset calibration. A good
thermometer or a temperature simulator should be
used to properly adjust this parameter.

Advertising