TROUBLESHOOTING

DIAGNOSTICS

VERSION NUMBER
The version number of the software is the first item shown in the DIAGNOSTICS menu. You will need this informa-

tion if you call for technical support.

BREAKER STATUS
You can check the status of each breaker from this menu item. You will see OFF, ON or NO RESPONSE. The latter

will be displayed if the breaker has been set to MAN at the panel, it is in the off or tripped positions, or the breaker is
not installed or is defective.

BREAKER TEST
You can test breakers directly from the Interface Module by using the BREAKER TEST function in the DIAGNOS-

TICS section. Use the

à or Ä buttons to select the breaker and then press OK. That breaker will be ‘flashed’ once.

That is if the breaker is off, it is turned on for approximately one second, then turned off again. If the breaker is al-
ready on, the opposite action takes place.

OFF Threshold

ON Threshold

65%

75%

45%

55%

25%

35%

Press OK to set the selected threshold.

DMXPowerPanel

Installation & Configuration

COMM ERROR

Verify wiring from DMXPowerPanel to EXP port on the POWERLINK panel

Verify that the green LED inside TERM compartment on the POWERLINK
panel is flashing. If not, the POWERLINK control module is not powered or is
defective..

No DMX Control

Ensure that the DMX control unit is sending DMX and that channels/dimmers
at the controller are patched correctly

Ensure that breakers are correctly addressed in the Interface Module

Check to see that the red RxD LED inside the Interface Module is flashing,
indicating that DMX is being received.

Interface Module doesn’t
start up

Check power connections

Check the green RUN LED inside Interface Module. If LED is not on, return
module for replacement.

POWERLINK

®

is a registered mark of Square D, Groupe Schneider

PANEL CONFIGURATION

CONTINUED

SET THRESHOLD
When a DMX signal is used to control relays or breakers, on or off operation occurs as the DMX signal levels pass

through the ‘threshold’ that has been set by the user.

To set the DMX thresholds for the panel, go to the CONFIGURATION menu and select SET THRESHOLD.