Decrement RH Output - This DIP switch will allow you to calibrate the sensor through the software. The switch
must be toggled from the Off to the On position and then returned to the Off position for a
decrease of 0.5% RH. This means that if your humidity has drifted 1% over a certain time
period, you will be able to toggle the Decrement RH Output switch 2 times in order to
slide the whole curve downward. Note: This is only a single point calibration, and is not
recommended for critical applications. Please contact the factory before doing any
field calibration.
Reset to Original Calibration - Both the Increment and the Decrement DIP switches should be turned on for a
minimum of 5 seconds before turning them both off again. This will allow you to reset
the transmitter back to the original factory calibration.

RH Duct and Outside Wiring Diagram (For Combination Units and NEMA Rated Enclosures)

ACI recommends that the ACI/RH 4-20 mA Duct and Outside relative humidity transmitters be wired with a two-wire,
16-22 AWG twisted pair or shielded cable for best results. All ACI/RH Duct and Outside voltage output or AC powered
current output transmitters should be used with a 3-wire, 16-22 AWG shielded cable. Note: When using a shielded
cable, be sure to connect only (1) end of the shield to ground at the controller. Connecting both ends of the shield to
ground may cause a ground loop.

1

2

3

4

ON

4

5

6

3

2

ON

1

SW2

SW3

J2

4-20

GND

VDC

Vout

Relative Humidity Sensor
(Polarized Male Connector
See Figure #8 above)

Span Adjust

Potentiometer

Zero Adjust
Potentiometer

Red Wire

BLK Wire

Green Wire

DC Power

AC Power

2

2

Figure # 5

Output Selection Switches (SW3)

4-20mA Out

4-20mA Out

3

4

4

3

AC/DC Power

AC/DC Power

0-10 VDC

0-5 VDC Out

ON

1

ON

1

4

4

3

3

ON

2

2

1

1

ON

Test and Calibration Switch Settings (SW2)

100% RH Output

50% RH Output

0% RH Output

Figure # 6

6

6

6

5

4

5

5

4

4

Normal Operating Condition

Reset to Original Calibration

Decrement RH Output

Increment RH Output

ON

ON

ON

3

2

3

3

2

2

6

1

5

1

1

4

3

2

1

ON

4

4

4

5

6

5

5

6

6

3

2

3

3

2

2

ON

1

ON

1

1

ON

Figure # 4

Figure # 8

J2

Push tab in and pull up on the Sensor
cable to remove from J2 Connector

J3

For ACI programming use only !

R

e

d

B

la

ck

G

re

en

Advertising