Installation and Operation Instructions

ACI/RH TUCH LCD Room Unit

GENERAL INFORMATION
The ACI/RH TUCH LCD Room Unit is factory-
configured to support your specific requirements.

CAUTION
• CHECK THAT THE ACI/RH TUCH LCD ROOM

UNIT IS CORRECTLY CONFIGURED FOR THE
APPLICATION; CONTACT ACI IF YOU ARE
UNSURE.


• THE ACI/RH TUCH LCD ROOM UNIT IS A

PRECISION INSTRUMENT; PLEASE HANDLE
IT WITH CARE!

MOUNTING INSTRUCTIONS
Separate the cover from the base. Attach the base
directly to drywall, or to a standard 2” x 4” junction box
using the mounting hardware provided. Refer to the
wiring instructions to make the necessary connections.
After wiring, attach the cover to the base and turn the
(2) hex-screws at the bottom of the base until the cover
cannot be removed.

WARNING
• REMOVE POWER BEFORE WIRING! NEVER

CONNECT OR DISCONNECT WIRING WITH
POWER APPLIED. DO NOT ALLOW LIVE
WIRES TO TOUCH THE CIRCUIT BOARD!


CAUTION
• WIRING MUST COMPLY WITH APPLICABLE

LOCAL AND NATIONAL ELECTRICAL
REGULATIONS.


• DO NOT RUN THE ACI/RH TUCH LCD ROOM

UNIT WIRING IN ANY CONDUIT WITH
MAINS POWER SYSTEM WIRING.


• ACI RECOMMENDS USING A SEPARATE UL-

LISTED CLASS 2 TRANSFORMER WHEN
POWERING THE ACI/RH TUCH LCD ROOM
UNIT WITH 24VAC! FAILURE TO WIRE
DEVICES WITH THE CORRECT POLARITY
WHEN USING A SHARED TRANSFORMER
MAY RESULT IN DAMAGE TO ANY DEVICE
POWERED BY THE SHARED TRANSFORMER.



WIRING INSTRUCTIONS
The number of wires needed to connect the ACI/RH
TUCH LCD Room Unit to a controller depends on the
application. Most applications require three wires to
support the RH output, power, and ground (common).
All signals are common ground referenced. ACI
recommends 16-22 AWG twisted pair wires or
shielded cable for all sensor installations. Be sure to
connect the cable shield to the ground at the
controller ONLY.

WIRING DIAGRAM

RH/FAN
RH signal to controller.

COM (-)
Ground or signal common, 20-28Vac (-).

POWER (+)
+15 to +30VDC, or 20-28Vac (+). See notes.

NOTES:
1. If the ACI/RH TUCH LCD Room Unit has any output configured as 0-10V
or 2-10V, the voltage at the POWER(+) terminal must be at least +18VDC.