Barksdale UDS7-BX User Manual

Page 2

Advertising
background image

List of functions: (xxxx = 125% f. s.)

Dialog item Value

Description

MENÜ

-1...9999 Primary display, e.g. the value selected in the DISP menu appears here

DISP

.....

Display value which should be permanently in the display:

act

actual measured value

sp1

switching point SP1

sp2

switching point SP2

max

maximum peak value

min

minimum peak value

ACT.

-1...9999 Display of actual measured value in bar

UNIT

Fixing

the

unit

bar

bar = bar

The unit is shown in the display appr.

psi

psi x = psi x 10

every 30 sec. for appr. 5 sec.

psi

psi = psi

HPa

HPa = Hekto-Pascal

mbar

mbar = millibar

UND

Unit display “on” or “off”

SP.1 .....

none

switching output deactivated

wind

window technology

stnd

standard evaluation SP2

erro

error output

ON-1

-1 ... xxxx

Switch-on point for SP1; if the ON value is smaller than the OFF

value

the switching point evaluation is falling

OFF-1

-1 ... xxxx

Switch-off point for SP1

DLY1

0,0s...9,9s

Switch-on / switch-off delay for SP1 in seconds

INV-1

.....

Inversion of switching output SP1

hlfs

high-level-fail-save (normally open function)

Ilfs

low-level-fail-save (normally closed function)

SP.2

.....

none

switching output deactivated

wind

window technology

stnd

standard

evaluation

SP2

erro

error output

ON-2

-1 ... xxxx

Switch-on point for SP2;

if the ON value is smaller than the OFF value

the switching point evaluation is falling

OFF-2

-1 ... xxxx

Switch-off point for SP2

DLY2

0,0s...9,9s

Switch-on / switch-off delay for SP2 in seconds

INV-2

-----

Inversion of switching output SP2

hlfs

high-level-fail-save (normally open function)

Ilfs

low-level-fail-save (normally closed function)

MAX

-1 ... xxxx

Display of peak value

CLRH

-----

Delete the maximum value memory

-----

no deletion

clr

delete

value

3

2

Dialog item

Value

Description

CDLY

0,0s...9,9s

Time setting to delete the maximum value memory after switching

point SP1 is reached (manual deletion is still possible)

MIN

-1 ... xxxx

Display of peak value “Min“

CLRL

-----

Delete the minimum value memory

----- no deletion

clr

delete

value

OFFS

-9,9 ...+xx

Measured value offset in bar

CUT

0,0 ... +xx

Cut-off. e.g. signal suppression at measuring range start in bar

DLDS

0,0 ... 9,9s

Time delay for currently displayed value in seconds

ERRC ----- Error

messages:

0:

-ok-

no error

1:

max

exceeding pos. measuring range

2:

min

exceeding neg. measuring range

3:

dig1

switching output 1 error

4:

dig2

switching output 2 error

5:

anao

analog output error

6:

sens

sensor error

7:

data

data error (EEProm)

8:

prog

program error

9:

cal

calibration error

V7.X

Lev0...Lev2 Programming lock indication (see code)

Version display with actual input level:

0 :

only display of operating parameters, no changes possible

1 :

only switching points can be set (“max” and “min” memories)

2 :

release user level (all operating parameters for customer)

LITH

20 ... 100

Change display brightness 20...100%

(only for units with Dot-Matrix display)

AOZS

0 ... 9999

Scale the analog output - start value (e. g. 0 bar = 4 mA)

AOFS

0 ... 9999

Scale the analog output - end value (e. g. 400 bar = 20 mA)

(output signal start value always corresponds to the display initial

value, e. g. 0 bar = 4mA)

Maximum turn-down 4 : 1, i.e. at values below 25 % of the

measuring range the analog output is switched off

CODE 000...999

Security

Sequence

Lev1: 471

Allow to change switching point parameters only

Lev2: 740

Able to reconfi gure all allowable parameters

Lev0: 999

All parameters will be lock

OPT

-----

For internal use only

(onlyV7.X)

For models shipped before Nov. 23, 2013