3. Operating elements

Barksdale GmbH
Dorn-Assenheimer Strasse 27
D-61203 Reichelsheim / Germany

Tel.: +49 - 60 35 - 9 49-0
Fax: +49 - 60 35 - 9 49-111 and 9 49-113
e-mail: [email protected]
www.barksdale.de

UDS 3

1

2

Electrical
connection

1 = +Ub
2 = –Ub (*)
3 = Signal

Switch contacts

S1

S2

S3

S4

S1

S2

S3

S4

Protective
load

M4

Analog output

Analog-GND (0 V)

4...20 mA (0...10 V)

Current supply

+18 V DC...+30V DC

0 V

max. R

L

=

UB –12 V

20 mA

(max. 10 mA)

Sensor connection UAS 3

acc. DIN 43650

8-digit 14-segment display

Cover screws

Sign

Trend arrows

Menu buttons

20-part bargraph

Connection UAS 3

optional Pg 13,5

Pressure conn.

Pg 13,5

Pressure conn.

4 x ø4,5

Signal

+Ub

–Ub

1

2

3

gn

bn

ws

38,5

Switchpoint display SP1...SP4

Dimensions (in mm)

Operating Instructions Pressure Switch UDS 3 with 4 Relay Outputs
and Trip Amplifier UAS 3

1. Product description

2. Starting operations

Intended applications
- The pressure switch / trip amplifier is a device to monitor system pressure, temperature, flow, level,

etc. and has four switching outputs and one analog output.

- The pressure switch is only to be installed in systems where the maximum pressure Pmax is not

exceeded (according to the values on the type label).

- The trip amplifier is only to be connected to input signals according to the values on the type label at

the bottom side of the device.

- Attention: This device is not designed to be used as the only safety relevant element in pressurized

systems according PED 97/23/EC.

Only assemble or disassemble the device when depressurized!

- The pressure switch should be installed and operated only by authorized personel.
-

Front cover and device bottom form a function unit. Exchanging the parts can result in measuring errors
or malfunctioning. See serial number inside the front cover.

For wall mounting remove the four front cover

screws and the front cover. Then fasten the device with four screws to the wall and finally remount the
front cover. To damp strong vibrations shock mounts must be used.

- Mount the pressure connection (G 1/4 female) of the UDS 3 to the pressure system with a flexible pipe

and tighten with a 45 Nm torque. For pressure peaks damping screws must be used.

- UAS 3: Connect the sensor to the 3-pin cube plug at the bottom side of the device.
- The electrical connection (supply, analog output switching contacts) must be carried out according to

the connection tables depicted on the top of the device by removing the cover cap and insert the cable
through the cable gland PG 13,5. If required, additional cable glands can be installed in the cover cap
by breaking out the perforated cavities.

- The electrical connection must be carried out in accordance with the VDE 0100 regulations. In order to

ensure trouble-free operation it is essential to connect the protective lead.
When operating from 230 V AC loads at the switch contacts independent cables must be installed for
supply and switches (cover cap with two cable screw connections).

- If inductive loads (magnets, contactors, etc.) are connected to the switch relays, suitable protective

devices (varistors etc.) must be provided.

Fixing lugs (f

or M4 scre

ws)

Item-Nr.: 923-1196

Software version: V1. or higher

Index C, 08. 06. 2004

Specifications are subject to

changes without notice.

Contact rating

: max. 120 V DC / 250 V AC

Switching power

: max. 120 W / 1250 V AC

Switching capacitiy : 220 V AC / 3 A VDE 0660 T.2
Constant current

: max. 5 A

Switching rate

: max. 20/s

Analog measuring input
By choice:
Current input

: 4...20 mA

Voltage input

: 0...10 V DC

Resistance input

: Poti (500 Ohm...100 kOhm)

(*) in combination with 2-wire circuit pin 2 is not required.

Plug 3-pin
DIN 43650

38,5