Gas fireplaces, Winthrop – Avalon Stoves Winthrop HH User Manual

Page 3

Advertising
background image

Minimum Framing Dimensions - Rear Vent

Minimum Framing Dimensions - Rear Vent

A - Minimum 1/2” clearance
B - Minimum 1” clearance
C - 7-1/2” approximate, varies due to vent

installation
D - Most installations use:

- 6” vent section for 2 x 6 walls
- 4” vent section for 2 x 4 walls

Minimum 1/2” Clearance

Route the

electrical line
to a position

at the left

rear of the

fireplace

HH Minimum
enclosure height = 49

The on/off switch/thermostat wire (if used) should be
routed to a location near the right front of the fireplace

Minimum Framing Dimensions - Top Vent

The ON/OFF switch/thermostat wire (if used) should be routed to

a location near the right front of the fireplace

Route the
electrical line to
a position at the
left rear of the
fireplace

Firestop (required) comes with fireplace

Vent clearance (8” dia.
vent): 1” to the sides, 1”
below and 3” above the
vent to combustibles

HH Minimum
enclosure height = 49

15-1/2”

48” Min.

Minimum Framing Dimensions - Top Vent

41-1/4”

38-1/2”

20”

30-3/4”

38”

25-3/4”

38-1/2”

41-1/4”

20”

A

B

C

D

48” Min.

Winthrop

Gas Fireplaces

Winthrop

Gas Fireplaces

The Winthrop TRV is shown with the Victorian Lace Black Nickel Upgrade Face and Herringbone Fireback