WARNING

OIL SMART SIMPLEX SYSTEM

The Oil Smart Simplex System, when combined with
a manual sump pump, will automatically pump water
without the risk of pumping oil into the environment.
Additionally, the system alerts maintenance or
building personnel in the event of a high oil or high
water condition. Installation of the Simplex Panel
allows you to comply with Elevator Code ASME A17.1
and State/Federal regulations while reducing the risk
of adverse publicity, fines and expensive cleanup
costs.

FEATURES

Patented Oil Smart® and Liquid Smart® Controls with
20' cords and mounting brackets.

Indoor/Outdoor NEMA 4X Heavy Duty Polycarbonate
Enclosure: 10"x8"x4", color gray material 94V-2,
polycarbonate, IP-56 rating.

Voltage: 120/208/240 VAC single phase 50/60 hz

CSA International Certified No. 229294

External Mounting Feet: Quick installation

High liquid alarm with test and silence features, red
beacon alarm light, white light for water present,
yellow light for oil present, high 85 decibel audible
alarm. Complete dry contacts for each alarm
condition.

HOA switch and green light for pump run

ALL INSTALLATIONS MUST BE IN
ACCORDANCE WITH THE NATIONAL

ELECTRICAL CODE AND ANY OTHER APPLICABLE
STATE AND LOCAL ELECTRICAL REQUIREMENTS.

PANEL INSTALLATION

1. CAUTION: To maintain the NEMA 4X rating, make

all wiring connections with seal tight cable grips or
conduit connections to be supplied by end user.

2. Determine mounting location for control panel.

Mount panel using mounting feet supplied.

3. Determine hole location on panel for liquid-tight

or conduit connections. Attach connectors and
conduits.

4. If pump is present, it is important that the alarm

circuit is independent of the pump to assure that
the alarm will activate if pump circuit fails.

5. Run pump cable, Liquid Smart® cable, and

Oil Smart® cable through conduit. Make field
connections as shown on wiring diagram (see page
3).

6. Run power line conductor through conduit. Wire

to terminals per enclosed schematic. Branch circuit
protection to be provided by end-user.

COMPONENTS INSTALLATION

1. The Oil Smart Pump Switch and Liquid Smart Alarm

Sensor shall be mounted in a clean environment,
clear of mud and all metallic debris.

2. The switches shall be installed where the water

intrusion will not directly contact or splash the white
plastic case.

3. Mud or other conductive materials left on the body

of the switches will hamper its operation; take effort
to clean the switch prior to initial installation.

4. Mount with enclosed mounting brackets. Note:

Keep sensors at least 2" clear of any metallic
material.

TESTING

Liquid Smart® Alarm Sensor: Fill small cup supplied
with oil. Submerge only the plastic lens (optic sensor)
into oil, the alarm will activate showing oil present
(yellow light). Now touch finger to the exposed
stainless steel sensor, the alarm will show water
present (white light) will turn on.