Unit Physical Data

Model

036

060

120

Compressor (qty)

Scroll (1)

Scroll (2)

Factory Charge R410A (lbs) [kg] Per Circuit

4.5 [2.04]

5.5 [2.49]

5.5 [2.49]

Water Connection Size

Source/Load (in)

Residential

1" Swivel

1” Swivel

1-1/2 IPT

Commercial

3/4” IPT

1” IPT

HWG (in)

Residential

1" Swivel

1” Swivel

1/2" IPT

Commercial

1/2” IPT

1/2” IPT

Weight - Operating (lbs) [kg]

348 [158]

360 [163]

726 [329]

Weight - Packaged (lbs) [kg]

373 [169]

385 [175]

770 [349]

Water Volume (Source)

Gallons (Liters)

0.96 (3.64)

1.33 (5.04)

2.65 (10.02)

Dual isolated compressor mounting

Balanced port expansion valve (TXV)

Insulated Source and Load Water Coils standard

Insulated Refrigerant Circuit standard

Compressor on (green) and fault (red) light