InRow RD 10 kW Air Cooled Operation and Maintenance

36

1. Use Ping with a size of 113 bytes to assign the IP address defined by the ARP command. For the

IP address defined in step 1, use one of the following Ping commands:

– Windows command format:

ping 156.205.14.141 -l 113

– LINUX command format:

ping 156.205.14.141 -s 113

2. Use Telnet to access the Network Management Card at its newly assigned IP address. For

example:

telnet 156.205.14.141

3. Use apc for both user name and password.

See “Control console” on page 36 to finish the configuration.

Control console

After you log on at the control console, as described in“Local access to the control console” on page 35
or “Remote access to the control console” on page 35:

1. Choose Network from the Control Console menu.
2. Choose

TCP/IP

from the Network menu.

3. If you are not using a

BOOTP or DHCP

server to configure the

TCP/IP

settings, select the Boot

Mode menu and then select Manual boot mode.

4. Set the System

IP

, Subnet Mask, and Default Gateway address values. (Changes will take effect

when you log out.)

5. Press

E

NTER

to return to the

TCP/IP

menu.

6. Press

C

TRL

+C

to exit to the Control Console menu.

7. Log out (option 4 in the Control Console menu).

Note: If you disconnected a cable from the local computer during the procedure
described in “Local access to the control console” on page 35, reconnect that cable and
restart the associated service.