ConTech Lighting CL8 User Manual

ConTech Lighting For the car

Advertising
background image

For the ConTech Lighting 6” and 8” Ceiling Mount Integrated LED Cylinder Series: CL6 and CL8

INSTALLATION PROCEDURES

Before attempting installation please refer to your local electrical code.
1. Detach the cylinder lid from the fixture by twisting the lid clockwise and

pull it up.

2. Remove cylinder tether from lid and attach lid to junction box.
3. Re-attach cylinder tether to lid to aid wiring. Figure 1
4. Cylinder housing may contain multiple wires, depending upon dimming or

non-dimming option being installed.

5. Connect cylinder black (hot) wire to junction box hot wire, and connect

cylinder white (neutral) to junction box neutral wire. Connect cylinder

green ground wire to either junction box ground wire or ground screw.

6. For cylinders with 12D1 in catalog number [Standard Triac Dimming], the

driver can be dimmed with many quality 120V incandescent and

electronic low voltage dimmers without additional wiring.

7. For cylinders with MVD2 in catalog number (0-10V Dimming), the driver

can be dimmed with 0-10V dimming controls. Locate low voltage

dimming control wires (purple, gray) in cylinder and make appropriate

connections, purple to Dim+ junction box lead and gray to Dim- junction

box lead. For Non-Dimming applications, leave the dimming control wires

(purple and gray) capped inside the cylinder. Note: When using 0-10V

dimming drivers, Class I wiring (300V wiring inside conduit) is required.

Please consult factory for additional details.

8. For cylinders with 12D3 in catalog number, the driver (Lutron Hi-Lume

A-Series LTE) is compatible with various Lutron forward phase dimming

controls. Contact Lutron for the up-to-date compatibility list of dimming

controls: www.lutron.com. Also note for cylinders with 12D3 in catalog

number, an additional ground connection is required to ground the driver

case, ensure that the (2) two cylinder ground wires are either wired to

junction box ground wire or ground screw.

9. Be sure not to pinch wires when attaching cylinder to lid. Engage cylinder

to lid then turn cylinder counter-clockwise until it stops.

LED MODULE AND REFLECTOR INSTALLATION:

1. Remove protective cover from LED module.
2. Attach reflector to LED module by aligning tabs, then twist and lock into

place. Figure 2

3. Make the LED module electrical connection. Figure 3
4. Push LED module/reflector assembly into cylinder until reflector flange

seats firmly against cylinder face. Cylinder spring clips secure

module/reflector assembly in place.

5. For wet location installations: Attach gasketed trim ring with the four

(4) provided Philips head screws.

IMPORTANT SAFETY INSTRUCTIONS:

• Read all the instructions before installation. Save instructions for later use.

• Turn off power at fuse or circuit breaker box before installation or before doing any

maintenance work.

• Product must be grounded to avoid potential electric shock and any other potential

hazards.

• Product must be mounted in locations and at heights and in a manner consistent

with its intended use, and in compliance with National Electrical Code and local

codes. Use of accessory equipment is not recommended.

• Installing contrary to instructions may cause unsafe conditions.

• Do not block light from the trim aperture, in whole or in part, as this may cause

unsafe conditions.

• Warning: Risk of fire. Most dwellings built before 1985 have supply wire rated at

60°C. Consult a qualified electrician before installation.

• Avoid hazards to children: account for all parts and properly dispose of all packing

materials.

• Call the Technical Support department at Con-Tech Lighting with any installation

questions: 847.559.5500

LEDCYLINST CM

www.contechlighting.com

All specifications subject to change without notice.