Connect sensors and sensor pods to a-link ports – APC NETBOTZ NBWL0455 User Manual

Page 18

Advertising
background image

14

NetBotz 455 Installation and Quick Configuration Manual

Connect Sensors and Sensor Pods to A-Link Ports

You can cascade up to a combined total of two NetBotz Rack Sensor Pod 150s
(NBPD0150) and NetBotz Room Sensor Pod 155s (NBPD0155) and up to a
combined total of eight Temperature Sensors with Digital Display (AP9520T)
and Temperature/Humidity Sensors with Digital Display (AP9520TH). You
cannot cascade appliances. Use one appliance per system. A-Link is an APC
proprietary CAN (Controller Area Network) bus. Devices compatible with
A-Link are not Ethernet devices and cannot coexist on an Ethernet bus with
other networking devices, such as hubs and switches.

Before performing this procedure, follow the installation instructions provided
with the devices you are cascading.

1. Connect sensors

and sensor pods to
the appliance as
shown.
– Use CAT-5 (or

equivalent)
Ethernet patch
cables (



.

Caution: Do not
use crossover
cables.

– Connect to in

and out ports as
shown.

– The maximum

combined length
of all A-Link
cables must not
exceed 1000 m
(3,280 ft).