For Con-Tech Lighting 6" Recessed Metal Halide Housings

www.con-techlighting.com

All specifications subject to change without notice.

1-847-559-5500

This document can be recycled.

INSTALLATION PROCEDURES

Housing can NOT be installed in direct contact with insulation. Do not install

insulation within 3" of fixture sides or wiring compartment, nor above fixture

in such a manner to entrap heat. (Figure 1)
NEW CONSTRUCTION INSTALLATION:

Install hanger bars to fixture, ensure end tab is facing outward. (Figure 2)

Extend bar hangers to fit between joists and position fixture temporarily by

hammering nail on bars into the joists. Hangers should be level with bottom

of joists (Figure 3). Locate center of fixture opening in the ceiling sheetrock

and cute a 6-1/2" hole for 6" fixtures, or a 8-1/8" hole for 8" fixtures.

NEW CONSTRUCTION INSTALLATION:

Locate proposed fixture center in ceiling tile and cut a 6-1/2" hole for 6"

fixtures, or a 8-1/8" hole for 8" fixtures. Place ceiling tile in T-Bar grid. Place

fixture into position and snap bar hanger foot with integral T-bar clips onto

T-bars (Figure 4). Secure hanger bars to T-bars and properly support the

fixture from the building structure. Note: Op-tional T-Bar Clips and screws

may be used as local code authority or site conditions require. To secure

fixture position in ceiling, squeeze tabs into hanger bars.

ELECTRICAL CONNECTION:

Remove J-box cover by pushing up on spring clip. Attach conduit with

connector to J-box and secure. Connect supply wires to fixture wires and

insulate with proper size wire nuts (not provided). Connect black to black

(hot), white to white (neutral), and green to green (ground). After splicing is

completed, insert wires carefully into junction box. Replace cover.

BALLAST REPLACEMENT:

If the ballast is not working properly, replace with the same ballast type.

Make sure that power to the fixture is off. Remove lamp. Pull trim and drop

the reflector from housing frame. Remove J-box cover with ballast attached

by pushing up on spring clip. Disconnect the ballast from input wiring and

lampholder leads (leads are terminated by wire nuts, or push to release

connectors on the ballast). Replace ballast with a factory approved ballast.

Resinstall ballast/J-box cover.

Use only those trims, lamps and maximum wattages proper for this fixture,

as indicated on the label within the housing. Do not exceed maximum

wattage lamp shown for each trim.
The National Electrical Code, Article 110-3(B), states that “Listed or labeled

equipment shall be used or installed in accordance with any instructions

included in the listing or labeling.” Use only with Con-Tech UL listed trims.

Use of other trims not listed in this fixture, including those that are UL classi-

fied, is a violation of N.E.C. 110-3(B) and voids all warranties.

IMPORTANT SAFETY INSTRUCTIONS:

• Read all the instructions before installation. Save instructions for later use.

• Turn off power at fuse or circuit breaker box before installation or before

doing any maintenance work.

• Product must be grounded to avoid potential electric shock and any other

potential hazards.

• Product must be mounted in locations and at heights and in a manner

consistent with its intended use, and in compliance with National Electrical

Code and local codes. Use of accessory equipment is not recommended.

• Installing contrary to instructions may cause unsafe conditions.

• Do not block light from the trim aperture, in whole or in part, as this may

cause unsafe conditions.

Warning: Risk of fire. Most dwellings built before 1985 have supply wire

rated at 60°C. Consult a qualified electrician before installation.

• To avoid hazards to children, account for all parts and properly dispose of

all packing materials.

• Call the Technical Support department at Con-Tech Lighting with any

installation questions: 847.559.5500.

White to White

Black to Black

Ground Wire

Nail In Tabs

Bar Hanger

Joist

Optional T-Bar Clip

Note: Tighten screw to secure

hanger bar to T-Bar

Bar Hanger

T-Bar

JOIST: 2" x 8"

3"

INSULATION

CEILING MATERIAL

5