ConTech Lighting REXA User Manual

Recessed mount

Advertising
background image

REXA INST

Con-Tech Lighting REXA Series Adjustable Recessed or Surface Mount LED Edge-Lit Exit Sign with Battery Back-Up

www.con-techlighting.com

All specifications subject to change without notice.

1-847-559-5500

This document can be recycled.

INSTALLATION INSTRUCTIONS:

The unit can be installed on any surface, you may rotate the Exit panel in any angle from 0 - 180°. Secure Exit panel angle using the locking screws.

Recessed Mounting: Ceiling/Wall

1. Refer to assembly drawing before starting installation. (Figure 1)
2. Position metal housing and bar hangers between joists. Make sure bar hangers are oriented in the correct position. Position metal housing

temporarily by hammering “nail-in” tabs on bar hangers, then secure permanently with nails. Bar hangers should be level with the bottom

of the joists. (Figure 2)

3. Adjust height of metal housing vertically using adjusting slots and tightening all screws on adjusting slots and bar hanger bracket to secure

adjusting bracket and bar hanger.

4. Connect test switch and LED indicator cables via connectors. (Figure 1) You must connect battery connectors before connecting AC power.
5. Make proper electrical connections at recessed metal box or at junction box in the ceiling:

- Make the proper supply wire connections.

- If using 120VAC, connect the black and white wires to the supply wires. If using 277VAC, connect the orange and white wires to the

supply wires. (Figure 3)

- Cap off unused wires. In all cases, use standard approved wire nuts for connection of wires.

NOTE: You may use holding wire during wiring.

6. Determine direction for chevron (arrow) placement. Peel adhesive chevron(s) from backing liner and place into the marked position on the

template. Firmly press chevron corners and edges, then peel template off and leave chevron in place. NOTE: When Chevron(s) are being

taped on the EXIT panel, you can not use it again once it is removed.

7. Secure trim plate by using provided screws. (Figure 4)
8. Allow battery to charge for 24 hours before first use.
For recessed wall mounting, you may follow all procedures above, then rotate the EXIT panel 90º after securing the trim plate.

Recessed Back Box

(Metal Housing)

Bar Hangers

Spring Bracket

Main Backup Circuit

For AC

Power

Junction

Box

End Cap

Main Housing

Rotation Housing

Chevron

EXIT Panel

Chevron Template

Trim

Plate

Screw

Recessed Back Box

(Metal Housing)

Adjusting Slots

Bar Hangers

Tighten Screws After Positioning

Gr

een

Orange

White

Black

Ground

Wire

277VAC

Input

120VAC

Input

Recessed Ceiling Mount

Recessed Wall Mount

Recessed Mount