Technical features, Onepower line interactive ups – Atlantis Land OnePower Line Interactive UPS A03-S1501 User Manual

Page 48

Advertising
background image

OnePower Line Interactive UPS

A03-S1001/A03-S1501 Pag. 43

Technical Features

Model

A03-S1001

A03-S1501

Power Rating(VA)

1000

1500

Power Rating(W)

600

900

INPUT

Voltage:

170-287V

Frequency:

50Hz±5%

OUTPUT

Voltage:

230V(±10%) [AC] / 230V(±6%) [INV]

Frequency:

50Hz (±1%)

AVR

Built-in

Waveform

Simulated SineWave

TRANSFER Line/Battery

Less than 4 ms (typical)

EFFICIENCY

Total Efficiency Over 80%

BATTERY

Voltage

24VDC

Capacity

12V/7.0Ah

12V/9.0Ah

Quantity

2

Recharge Time

6-8 hours to (90%)

Type

Sealed Maintenance Free Lead Acid VRLA Type

INDICATORS(4 LED)

Utility Normal, Backup, Battery Low and Battery

Fault conditions

PROTECTION

Overload AC Buzzer continuously alarms

Overload Inverter UPS shuts down after 10

seconds(>110%)

Short Circuit INV Input Fuse & Electric Circuit

Short Circuit AC Electric Circuit

Battery Over-drain Two stages: Controlled Battery

Low Warning & Cut Off

Modem/Network RJ45 / RJ11

Spike Suppression Meets EN61000-4-5

Noise Suppression Meets EN50991-1

CONNECTIONS

Output 6 x IEC (Battery Power Supplied)

Computer USB

Backup Time

10 to 30 mins for typical PC Load

MECHANICAL

Dimensions
(WxHxD):

147 x 234 x 360 mm

Net
Weight(with
Battery):

13.5 Kg

16.5 Kg

ENVIRONMENTS

Temperature 0°-40° C

Humidity 0-95% (non-condensing)

CERTIFICATION

CE, FCC

Advertising