WIKA operating instructions differential pressure gauge models 712.15.100, 732.15.100

Defect

Possible reason

Remedy

No signal output

Failure of power supply

Check power supply and wiring

Wiring interrupted (or broken)

replace defective components

Transmitter incorrectly wired

Check wiring;
if necessary rectify it

No pressure

Check tailpipes

Open press. compensation valve

Close pressure compensation valve

Electronic defect e.g. through

Return pressure gauge to

incorrect supply voltage

manufacturer for repair

or stray voltage spikes

Steady signal

Pressure entry blocked

Check tailpipes and pressure entry

despite pressure

bore, if necessary clean it carefully

variation

Open press. compensation valve Close pressure compensation valve
Electronic defect e.g. through

Return pressure gauge to

incorrect supply voltage

manufacturer for repair

or stray voltage spikes
Transmitter defect after being

Return pressure gauge to

over-pressured

manufacturer for repair

Steady and too high

Electronic defect through

Return pressure gauge to

signal despite of

incorrect supply voltage

manufacturer for repair

pressure variation

or stray voltage spikes

Full span reading too low Supply voltage too low

Adjust supply voltage

Load impedance too high

Consider permissible max. load

Wrong scale selected

Check position of scale selection
switch

Zero signal too low

Wrong zero compensation

Readjust zero point

Zero signal too high

Wrong zero compensation

Readjust zero point

Transmitter over-pressured

Return pressure gauge to
manufacturer for repair