Commissioning, operation – WIKA A2G-70 User Manual

Page 11

Advertising
background image

WIKA operating instructions air2guide model A2G-70

11

GB

40202801.03 08/2012 GB/D/F/E/I

DR

W_TH0.05

UB 15-24 V=

GND / Temp Out 4-20 mA

UB 15-24 V=

GND / rF/rH Out 4-20 mA

Temp
.

Offset

rF / rH

Offset

Connection diagram for output 4 ... 20 mA (option)

Note

If only the humidity output is used, U

B

15 ... 24 V= (temp.) must be bridged to

U

B

15 ... 24 V= (rF/rH) and the temperature output "GND / Temp Out 4 ... 20 mA"

must be bridged to GND of the voltage supply.

6. Commissioning, operation

Mounting instructions

Max. air velocity 10 m/s

Notes for users

Due to air circulation, dirt and dust particles might occur on the sintered

filter that protects the sensors; these particles might impair the sensor

function. After dismounting the filter, it may be cleaned by blowing it out

using oil-free and filtered compressed air, ultrapure air or nitrogen or

washing it using distilled water. Filters that are too heavily soiled should

be replaced.

Do not touch the delicate humidity sensors as this voids warranty.

If used in aggressive gas atmospheres, an early recalibration or replace-

ment of the humidity sensors might be required. Such a recalibration or

possible sensor replacement is not covered by warranty.