WIKA CF1H User Manual

Page 28

Advertising
background image

Operating Instructions Temperature Indicating Controller CF1H

V 1.2

01/2007

- 28 -


Cooling action mode selection

Mode to select the Cooling action,

Selection

Air cooling, Oil cooling or Water cooling.

[Factory adjusted as Air cooling]

MODE

This display is indicated only when the option [D 2]

is

applied.


Air cooling (linear characteristic)

Oil cooling (The 1.5th power of Air cooling characteristic)

Water cooling (The 2nd power of Air cooling characteristic)

Cooling output

Mode to set high limit value of the cooling output.

high limit setting

Setting range:

Setting value

Cooling output low limit value to 105 %

Setting greater than 100 % is effective to the type

MODE Current

output.

[Factory adjusted as 100 %]

This display is not indicated when the option [D 2]

is not applied, or when ON/OFF action of cooling side.

Cooling output

Mode to set the low limit value of the cooling output.

low limit setting

Setting range: –5 % to cooling output high limit value

Setting value

Setting less than 0 % is effective to the type Current output.

[Factory adjusted as 0 %]

MODE

This display is not indicated when the option [D 2]

is not applied or when ON/OFF action of cooling side.

Cooling output ON/OFF

Mode to set the ON/OFF action hysteresis of the

action hysteresis setting

cooling control output.

Setting value

Setting range: 0.1 … 100.0 °C

[Factory adjusted as 1.0 °C]

MODE

This display is indicated when the ON/OFF action is

designated in Control action designation and when the

option [D 2] is applied.