Operation, Monitoring environmental conditions – Winland Electronics EA800-ip User Manual

Page 35

Advertising
background image

D-011-0152

35

Operation

This chapter provides instructions for doing the following:

“Monitoring Environmental Conditions” on page 35

“Viewing Sensor Settings” on page 36

“Viewing Active Alarms” on page 36

“Viewing the Alarm Log” on page 37

“Viewing the Event Log” on page 38

“Viewing the Sensor Log” on page 39

“Viewing Firmware Information” on page 39

“Viewing RF Information” on page 40

Monitoring Environmental Conditions

The current environmental conditions measured by each sensor connected to the EA800 console are shown on the

home screen. Depending on the current sensor status the home screen may be one of the following screens:

MONITORING screen: This screen is shown when there are no active alarms or pending alarms. This screen
displays the current readings from all programmed sensors as shown in the example below.

Note: Dashes indicate that a sensor has not been programmed yet.

MONITORING screen with pending alarm. A pending alarm indicates that
a sensor has exceeded the low or high limits but that the condition has
not exceeded the programmed delay (0 to 120 minutes). When an
alarm is pending, the sensor’s reading is displayed in inverse text as
shown in the example for wireless sensor 1.
If conditions in the sensor’s area return to the non-alarm state within
the alarm delay time, the text returns to normal. If conditions remain
outside the programmed sensor alarm limits for longer than the delay
time, the screen changes to the ACTIVE ALARMS screen below.

ACTIVE ALARMS Screen: This screen is displayed when conditions
monitored by any programmed sensor exceed one of its programmed
limits for longer than the programmed delay period. Only the active
alarm(s) is displayed as shown in the example below. See “Viewing
Active Alarms” on page 36
for the procedure to access alarm
information.

This column shows
environmental readings
for wireless sensors 5-8.

This column shows
environmental readings
for wired sensors 1-4.

Sensor 1
Sensor 2
Sensor 3
Sensor 4
(not installed)

Current Date

Current Time

Sensor 5
Sensor 6
Sensor 7 (not installed)
Sensor 8

Pending alarm