SVR-1 Single-Phase Step Voltage Regulators

28-10

Copyright © 2011 Howard Industries, Inc.

5

Document No. 2.4.132

Revision: 0

Issued: October, 2011

Howard Industries, Inc.

Laurel, MS 39440

www.howardtransformers.com

range. This is accomplished by setting

the raise (boost) and lower (buck) limit

switches (Figure 7) located on the tap

position indicator to prevent the tap

changer from traveling above or below

the desired settings. Scales on the

limit switches are graduated in percent

regulation, including 5%, 6-1/4%m

7-1/2%, 8-3/4% and 10% regulation

settings. Table 2 (Page 7) lists the load

current and regulation ranges available

with the HI-AMP

feature. At each

setting, a detent stop provides positive

adjustment. Upper and lower limits

need not be the same.

Upper and lower limits can also be

implemented with the digital control

unit.

_________________________________

SURGE ARRESTERS

Series Arrester

Each SVR-1 regulator is equipped

with an appropriately sized MOV-type

surge arrester connected between the

source and load bushings (Figure 4).

This series arrester (also known as a

bypass arrester) is provided to protect

the series winding of the regulator from

damage due to line surges, such as can

result from lightning, switching surges,

and line faults. The series arrester

alone does not provide complete

lightning protection. For more complete

protection, option shunt arresters

should be installed.

Shunt Arresters
MOV surge arresters are available as an

option on the SVR-1 regulator to provide

protection for the shunt winding. Shunt

arresters are mounted on the regulator

tank adjacent to the load bushing and

the source bushing. Each arrester

is connected between the bushing

terminal and ground.

FIGURE 7: HI-AMP

limit switches

(one located on each side of tap

position indicator)

Advertising