DTS Series Cooling Units

3

SECTION 3: HANDLING

3.1 Transporting

The cooling unit shall only be moved in the fully

assembled, upright condition.

If the cooling unit is being shipped with an electrical

panel enclosure it shall be packed separately from

the electrical enclosure.

WARNING!

If for any reason the cooling unit has been

placed in any position other than fully upright

it shall be placed in a vertical position for a

minimum of 1 hour prior to starting the unit. If

this is not done the compressor may be drained

of oil. Operation of the compressor without

proper oil fill may cause permanent damage to

the cooling unit and void the warranty.

3.2 Storage

The cooling unit shall not be exposed to

temperatures exceeding +70ºC. Store the unit fully

assembled in the fully upright condition.

WARNING!

Failure to observe these requirements

will void the warranty.

SECTION 4: INSTALLATION

4.1 Pre-installation testing

Before mounting the cooling unit to the electrical

panel enclosure it should be tested to verify function.

4.2 Installation onto the electrical panel

Before connecting the cooling unit to the power

supply, verify that the following are correct.

Voltage must be within ± 10% of the value listed on

the ID plate.

Voltage frequency must be within ± 3 Hz of the value

listed on the ID plate

Ambient temperature must be below +55ºC (for

options see “setting the operating parameters”

section)

Place the drilling template supplied with the cooling

unit onto the applicable mounting surface of the

electrical panel enclosure.

WARNING!

Metal chips from drilling and cutting the openings

may damage the electrical panel enclosure. Take

precautions required to prevent chips and debris

from getting into the enclosure.

WARNING!

Watch out for sharp edges created when drilling

and/or cutting the enclosure.

Drill holes in the electrical panel enclosure to

match the unit and cut out air flow openings.

Remove the cooling unit cover for handling during

installation by removing the cover mounting screws.

Install the two supplied stud bolts (in the accessory

pack) into the top two mounting hole locations of

the cooling unit.

WARNING!

Please note the information on the “Thread

Reach for Set Screw” label attached to the

cooling unit. If the noted installed thread depth

is exceeded the cooling unit may be damaged.

Install the cooling unit mounting insulation strips (in