8

5000 VA models:
Terminal Mode is a menu driven interface that enables enhanced configuration of the UPS.

Connect the serial cable to the serial port on the back of the UPS.

When using PowerChute

®

Network Shutdown software:

1. Open a terminal program. Example: HyperTerminal

From the Desktop, go to Start => Programs => Accessories => Communication
=>HyperTerminal.

2. Double-click

on

the

HyperTerminal icon.

Follow the prompts to choose a name and select an icon. Disregard the message, “...must
install a modem,” if it is displayed. Click OK.

Select the COM port that is connected to your UPS. The port settings are:

bits per second - 2400

data - bits 8

parity - none

stop bit - 1

flow control - none

Press Enter

3. Example for setting the number of external battery packs (SURT192XLBP):

Once the blank terminal window is open, follow these steps to enter the number of battery packs:

Press Enter to initiate terminal mode. Press Enter multiple times, until the prompt User
Name:
is displayed. Follow the prompts. Type slowly, waiting until each character appears
on the screen prior to typing the next character.
Web/SNMP Card defaults:

User Name: apc

Password: apc

Press 1 and Enter to select Device Manager.

Select the model by entering the corresponding number, then press ENTER.

Press 3 and Enter to select Configuration.

Press 1 and Enter to select Battery.

Press 2 and Enter to change the Battery Settings.

Type in the number of external battery packs (four battery modules per
pack), then press Enter. (Number of packs: 1= internal battery module, 2 = 1
SURT192XLBP, 3 = 2 SURT192XLBP, etc.)

Press 3 and Enter to accept the changes.

Press ESC multiple times (5) to return to the main menu.

Press 4 and Enter to log out.