Testing the Sensor
Detectors must be tested after installation and following periodic
maintenance. The Model #1008-4 may be tested as follows:

A. Test Switch

1. A recessed test switch is located on the detector housing (see

Figure 10).

2. Push and hold the recessed test switch for a minimum of 5

seconds. Use a small screwdriver or Allen key with maximum
diameter of 0.18 inch (the detector will trigger and then the smoke
detector will go into alarm thus sending a transmitting signal to
the receiver. If the tool is removed from the recessed switch the
sounder will shut off)

If the detector is within the listed sensitivity limits, the LED on the
detector should blink once per second and the horn should sound
within 3 seconds.