1. Introduction

The KT-MOD-INP16 is an input module that adds up to 16 zones

to the KT-400 controller. The module supports daisy chaining;

you can interconnect up to 15 KT-MOD-INP16 modules for a total

of 240 external inputs per KT-400. Adding the 16 onboard inputs

of the KT-400 gives a total of 256 inputs per KT-400. Combining

input and output expansion modules gives the flexibility to

connect up to 256 inputs and 256 outputs.
Note 1: The KT-400 SPI port maximum current draw, when the

12V AUX terminals are not used, is 500 mA.
Note 2: External power supply (12 VDC, 2 Amps) is required

when the total current draw exceeds 500mA on the SPI Port.

2. Specifications

Maximum Current Draw: up to 40 mA per module

Supports single end-of-line (5600 ohm resistors) and
no end-of-line (DRY) zone loops

Supports Normally Closed (NC) and Normally Open (NO)

contacts

The C (Common) terminal is +12 VDC

Input change with a debouncing of 500 ms (Slow) or
150 ms (Fast)

Reports one condition per input: SECURE or ALARM

Can be used for contact or elevator input

Cannot be connected to output modules KT-MOD-REL8 and

KT-MOD-OUT16 through SPI OUT, only through its SPI EXP

expansion port

3.

Installing the KT-MOD-INP16 Module

3.1. Unpacking
The KT-MOD-INP16 package includes the following parts:

One (1) KT-MOD-INP16 module, 14 cm x 8 cm (5.7 in x 3.25
in)

One (1) SPI cable with 1 SPI connector, 41 cm (16 in)

Four (4) plastic standoffs

Two (2) installation sheets, English and French

3.2. Mounting
The KT-MOD-INP16 can be installed inside a compatible cabinet

(KT-MOD-CAB or KT-400) or mounted in a dry and secure

location at less than 1 m (3 ft) from the KT-400.
1. Press the four (4) plastic standoffs through the mounting

holes of the cabinet,

2. Secure the cabinet to the wall in the desired location. Use

appropriate wall anchors when securing the cabinet to
drywall, plaster, concrete, brick or other surfaces.

3. Press the module into the plastic standoffs to secure the

module to the cabinet.

3.3. SPI Wiring

Perform the following steps to complete wiring:

Note 1: Before beginning to wire the unit, ensure that all power

(AC transformer and battery) is disconnected from the KT-400.
Note 2:

If you are combining input and output modules through

the SPI EXP expansion port of the KT-MOD-INP16, the input

module must be the 1

st

module connected to the KT-400 SPI

Port.

1. Connect the 6-pin SPI connector to the KT-400 SPI port or to

the SPI OUT of the previous KT-MOD-INP16 module.

2. Connect the six SPI wires (blue (BLU), white (WHT), green

(GRN), yellow (YEL), black (BLK) and red (RED)) to the SPI

IN (TB1) terminals.

3. You can use the SPI EXP of the 1

st

KT-MOD-INP16 to start a

group of output modules (KT-MOD-REL8 and KT-MOD-

OUT16 only).

4. Connect the 6-pin SPI connector from the SPI OUT to the

next KT-MOD-INP16 module.

5. Complete all zone wiring to the zone input terminals (Z1-Z16).

3.4. Check the power jumper JP5 position. Put it on EXT if you

need external power or INT if no external power is required.