www.americanaldes.com eml: [email protected]

PRODUCT

SPECIFICATIONS

AND ENGINEERING

INFORMATION

-----

SUBMITTAL DATA

MATHEWS GRAPHIC DESIGN - 941-358-0862

THERMALLY CONDUCTIVE,
PATENTED ALUMINUM CORE
The cross-flow heat recovery core
transfers heat between the two air-
streams. It is easily removed for
cleaning or service.

MOTORS AND BLOWERS
Each air stream has an indepen-
dent motorized impeller. 3 speed
operation 120VAC

FILTERS
Washable air filters in exhaust and supply air streams.
MOUNTING THE HRV
Four threaded inserts at corners of case designed to accept four rein-
forced polyester straps that are supplied with the unit.
DEFROST
Recirculating damper defrost system. Exhaust air is periodically cir-
culated through the unit to defrost the core.
CASE
Twenty gauge prepainted galvanized steel (G60) for superior corro-
sion resistance. Insulated to prevent exterior condensation. Drain
connections- 1/2" (12 mm) OD.
CONTROLS - HRV System Control
HRV defaults to LOW SPEED when plugged in. HIGH SPEED is ac-
cessible by connecting remote controls to designated terminals in-
side electrical box of HRV.
Standard LOW SPEED SETTING can be increased by manipulating
switches in electrical box. OFF/HIGH speed operation also available
by manipulating switches.
WEIGHT
42 lbs. (19 kg.) SHIPPING WEIGHT 45 lbs. (20.5 kg.)
ORDERING INFORMATION
PART NUMBER: 28 051

OPTIONAL ACCESSORIES:

28 884

20 Minute Fan timer -- White, Decora style (3 wire) 20
gauge wire (min.) 100' length (max.)

28 998

60 min. Twist Timer with hold, white Decora style

22 025

Weather Hoods, 2 - 5 (125mm) c/w 1/4 (6mm) screen

28 883

Dehumidistat Ventilation Control - Dehumidistat with
ON/OFF

28 882

Dehumidistat Control - Dehumidistat

All units conform to CSA and UL standards.
DUCT CONNECTIONS

5" duct connections.

DIMENSIONS inches

PERFORMANCE

E.S.P. (in.wg.)

CFM

L/S

0.1

143

68

0.2

138

65

0.3

132

62

0.4

128

61

0.5

123

58

0.6

116

55

0.7

113

54

0.8

106

50

0.9

103

48

1.0

97

46

Max. Temperature Recovery

72%

Sensible Effectiveness @70 CFM (32°F):

68%

Sensible Efficiency @70 CFM (32°F):

59%

Sensible Efficiency @67 CFM (-13°F):

56%

VAC @ 60 Hz:

120

Watts / Low Speed:

70

Watts / High Speed:

160

Amp Rating

1.5

HRV 120SRD

HEAT RECOVERY VENTILATOR

# 28 051

2

Advertising