2. Electrical Service Specifications

IMPORTANT: The dryer must be connected to the electric supply shown on the data label that is

affixed to the back side of the upper or top control door. In the case of 208 VAC or
230/240 VAC, the supply voltage must match the electric service specifications of
the data label exactly.

IMPORTANT: The wire size must be properly sized to handle the related current.

WARNING: 208 VAC and 230/240 VAC ARE NOT THE SAME. Any damage done to dryer

components due to improper voltage connections will automatically VOID THE
WARRANTY.

NOTE: ADC reserves the right to make changes in specifications at any time, without notice or

obligation.

MLG-96HS

E

LECTRIC AL

S

ERVIC E

S

PECIFIC ATION S

(

PER DRYER

)*

SERVICE

VOLTAGE

PHASE

WIRE

SERVICE

MINIMUM

WIRE SIZE**

APPROX.

AMP DRAW

CIRCUIT

BREAKER

60 Hz

50 Hz

60 Hz 50 Hz

2 0 8

3 ш

3/4

12

13.5

--

25

--

2 4 0

3 ш

3

12

12.5

--

25

--

380-400

3 ш

3/4

14

--

6.9

--

15

416

3 ш

3/4

14

--

6.6

--

15

460/480

3 ш

3/4

14

6.8

--

15

--

*

Contact factory for information not listed.

** AWG Stranded Type Wire...for individual lenghts less than 100 feet. (Motor lead wire is recommanded.)