System setup, Supervisory control wiring, Câblage de contrôle – Briggs & Stratton 100 Amp Automatic Transfer Switch User Manual

Page 7: System setup supervisory control wiring

Advertising
background image

System Setup

You must perform the following on the control module
before operating the system:

• If generator is installed in an area regularly subjected to

temperatures below 40°F (4°C), select a 50 second
warm up time by moving jumper installed on JP2 from
‘20’ position to ‘50’ position.

• Place 2 position switch in ‘NG’ or ‘LP’ position,

whichever is appropriate for your system.

• Place 3 position switch to match KW rating of installed

generator.

Supervisory Control Wiring

1. Terminal strip on control module in transfer switch has

four connections for customer use. There are two sets
of “Normally Closed” contacts available. They will be
activated when generator power is required. These can
be used for supervisory control of large connected
loads on generator. Loads will be allowed to operate if
there is enough generator power available.

NOTE: There are two wireways provided to keep the
supervisory loads separated from each other.

2. Terminals “A-A” on control module are rated for 24 VAC

and air conditioner contactor control. Contacts are
connected in series with the air conditioner contactor
control circuit.

3. Terminals “B-B” on control module are rated for 1 Amp

125 VAC and installer supplied contactor to control a
large load. Example: electric hot water heater. Contacts
are connected in series with the contactor control
circuit.

4. Tighten all wire connections/fasteners to proper torque.

See inside transfer switch enclosure for proper torque
values.

7

A
A

Air Conditioner Contactor

24 VAC

B
B

Contactor

Neutral
(if applicable)

115 VAC

2 Position

Switch

3 Position

Switch

JP2

CT1 & CT2

Connectors

Supervisory

Contacts

Advertising