Step 5 -- check thermostat operation, T2sn – Bryant T2SNAC01 User Manual

Page 5

Advertising
background image

5

To Select:

1. Enter configuration mode (if not already there).
2. Use up and down buttons to display Option 21. The SET

icon should be off.

3. Press MODE button once. The SET icon will come on. The

display now shows Option 21 setting.

4. Use up and down buttons to move between available

Option 21 choices of ON or OF. Factory default is OF.

5. Press MODE button again to return to Option 21. The SET

icon will now be off.

6. Use up and down buttons to select another Option, or press

FAN button to exit configuration mode.

Installer Test Mode
Installer test will be initiated by pressing the fan button for 20

seconds (15 seconds will enter installer setup) “InS” will appear on
the screen and the SERVICE icon will be illuminated.
In installer test mode, pressing the MODE button will change the
system operating mode. Note that AUTO mode is not available in

installer test. Heating and cooling modes must be tested
independently.

1. If the mode is set to HEAT, the first stage of heating will be

energized for three minutes (180 seconds), and then the first

and second stages (if a second stage exists) will turn on for
an additional three minutes. Installer test will always attempt

to run a second stage output whether it is attached or not,
providing a minimum of 6 minutes of first stage operation.

At the end of the 6 minute period, the MODE will return to
OFF.

2. Pressing the FAN button while the heating or cooling

equipment is not running will turn on the FAN relay and

display the FAN icon.

3. If the mode is set to COOL, the first stage of cooling turns

on for three, then first and second stages (if a second stage

exists) will turn on for three minutes.

4. If the mode is set to EHEAT, auxiliary heat turns on for

three minutes, then the mode returns to OFF.

Terminating Installer Test
After 15 minutes of inactivity (no button presses by the installer),

thermostat will automatically revert to normal operation. Pressing

RESET FILTER any time during installer test will terminate
installer test and return the thermostat to normal operation.

Step 5 -- Check Thermostat Operation

Fan Operation

1. Press FAN button, starting continuous fan operation. FAN

icon turns on.

2. Press FAN button again, stopping fan operation. FAN icon

turns off. (Some fan coils have 90 second fan off delay, so

fan may not stop immediately.)

Checklist

1. Run equipment through several heating and cooling cycles

to ensure proper operation.

2. If equipment is to be left in operation, setpoint and

operating mode must be properly selected.

3. Put away tools and instruments, and clean up debris.
4. Review Homeowner’s Guide with owner.
5. Leave literature packet with owner.

Table 2 – Non--Programmable --C Thermostat Quick Reference

THERMOSTAT OUTPUT

TSTAT

Model

Outdoor

Unit

Option

5

24V

Hot

Common

Fan

Heat

Stage 1

Heat

Stage 2

Cool

Stage 1

Reversing

Valve

T2SNAC01

AC

N/A

R

C

G

W

N/A

Y

N/A

T2SNHP01

HP

OFF

R

C

G

Y

W

Y

O/B

T2SNHP01

AC

ON

R

C

G

W

O/B

Y

N/A

Thermostat

Furnace

Air Conditioner

Heat

W

W

Cool

Y

Y

Y

Fan

G

G

24VAC

R

R

*Common

C

C

C

A08161

*Common connection not required if batteries are used.

Fig. 2 -- A/C Thermostat with Furnace

Thermostat

Furnace

Air Conditioner

Heat

W

W1

W2

Y1

Cool

Y

Y/Y2

Y

Fan

G

G

24VAC

R

R

HUM

Common

C

C

C

*

A08162

*Common connection not required if batteries are used.

Fig. 3 -- A/C Thermostat with 2--Stage or Variable

Speed Furnace

T2SN