Recommended Power Up/Down Sequence for Elevators Using DC SCR Controls

The following is a recommended sequence for turning on and off the elevator drive and
external OEM control. Figure 5-4 shows this sequence.

Figure 5-4 Typical Power Up/Down Sequence for DC SCR Controls.

M Contactor

Armature Enable

20msec

20msec

Field

“Drive ON”

Opto Output

Brake Release Signal

(from elevator controller)

50msec

Speed Command

50msec

RUN TIME

TURN-ON

TURN-OFF

Brake Set Time

Open

Closed

Open

Closed

Off

On

Off

On

Economy

Forcing

Running

Off

On

Disengaged

Engaged

Zero FPM

Contract Speed

Disengaged or “Picked Up”

Engaged or “Set”

Standing or Economy

Forcing or “Leveling”

Running

Sequence:

1.

Close the M Contactor. Approximately 20msec is required for the contacts to
close and connect the Control to the Motor and complete the armature loop.

2.

The filed is controlled independently of the armature. The field can be at
running voltage (or at forcing voltage) prior to actual commanding speed.

3.

Armature enable (pin J1-8 of the DC SCR Control) allows the SCR’s to begin
firing.

4.

The “Drive ON” Opto output from the DC SCR Control provides an indication
(for the elevator control) that the drive is ready to act on Speed or Torque
commands.

5.

Zero speed command should be held until the brake has actually disengaged,
allowing the car to move.