9. Connect generator “UTILITY 240 vAC” terminals to

transfer switch “UTILITY 240 vAC” terminals. Use

minimum #14 AWG conductors.

10. Tighten all wire connections/fasteners to proper torque.

See inside transfer switch enclosure for proper torque

values.

Supervisory Control Wiring

Terminal strip on control module in transfer switch has

four connections for customer use. There are two sets of

“Normally Closed” contacts available. They will be opened

when generator power is required. These can be used to lock

out large loads when powered by generator. Example: air

conditioner, hot water heater, etc..

1. Terminals on control module are for installer supplied

contactors to lock out large loads. Example: air

conditioner, electric hot water heater, etc.. Contacts are

connected in series with the contactor control circuit.

2. Tighten all wire connections/fasteners to proper torque.

See inside transfer switch enclosure for proper torque

values.

8

BRIGGSandSTRATTON.COM

A

A

B

B

Air Conditioner Contactor

24 vAC

Contactor

Neutral

120 vAC

Ground Bus

Main

To Generator

Neutral

Terminal

Supervisory

Contacts

To Utility Meter

Generator

Connection

Utility

Connection

Main Distribution Panel

Ground

Terminal

Neutral

Bus

Load

Connection

Model 071023