Installation – Broan Fresh Air System ERV90HCS User Manual

Page 16

Advertising
background image

3. INSTALLATION

(CONT’D)

3.9 I

NSTALLING

2 E

XTERIOR

H

OODS

Choose an appropriate location to install the exterior hoods:

• There must be a minimum distance of 6 feet (1.8 m) between the hoods to avoid cross-contamination
• There must be a minimum distance of 18 inches (457 mm) from the ground

Make sure the intake hood is at least 6 feet (1.8 m) away from the following:

• Dryer exhaust, high efficiency furnace vent, central vacuum vent

• Gas meter exhaust, gas barbecue grill

• Any exhaust from a combustion source

• Garbage bin and any other sources of contamination

Refer to figure below for connecting insulated ducts to the exterior hoods. An ‘’Anti-gust intake hood’’ should be installed in regions where
a lot of snow is expected to fall.

VD0028

T

APE AND DUCT TIE

O

PTIONAL

DUCT LOCATION

E

XHAUST HOOD

I

NTAKE HOOD

18’’

(457

MM

)

18’’

(457

MM

)

6’’ Ø

(152

MM

)

18’’

(457

MM

)

6’

(1.8

M

)

6’

(1.8

M

)

- 16 -