CONTROL FEATURES

CONTROL

DESCRIPTION

FAN SPEED

CONTROL

DEHUMIDISTAT

CONTROL

CONTINUOUS

MODE

INTERMITTENT

MODE

OneTouch

Yes

No

Yes

Yes

Basic

Yes

No

Yes

No

Standard

Yes

Yes

Yes

Yes

Basic Control:

Allows the user to manually set fan speed to low or high as required to maximize comfort.

Standard Control:

Offers automatic dehumidistat control and the option to select continuous or intermittent fan operation. Setting the wall control to low will
activate the continuous mode.

OneTouch Control:

Allows control of ventilator with the touch of a button. This control will operate as a main wall control. The OneTouch will operate the unit

in Intermittent Mode (20 minutes per hour), continuous low speed, continuous high speed, and off.

AUTOMATIC DEFROST CYCLE FEATURES

All models offer a non--electric defrost cycle feature which prevents frost and ice buildup within the heat recovery core. When the outside air

temperature falls below 23_F (--5_C) it is electronically sensed and the dampers close the outside air ports. This allows warm indoor air to

recirculate within the heat recovery core. The frequency of this cycle increases as the outside air temperature decreases.

MODEL

25_F TO 55_F

(---5_C TO ---15_C)

4_F TO ---17_F

(---15.6_C TO ---27.3_C)

BELOW ---18_F

(---27.8_C)

DEFROST*

EXCHANGE{

DEFROST*

EXCHANGE{

DEFROST*

EXCHANGE{

ERVBBLHA

6 Minutes

60 Minutes

6 Minutes

32 Minutes

6 Minutes

20 Minutes

HRVBBLHA

6 Minutes

60 Minutes

6 Minutes

32 Minutes

6 Minutes

20 Minutes

* All defrost times are in the standard mode (as shipped)
{

Time between defrost when within specified temperature range