8 engine governor adjustment, 1 7 kw units – Bryant Automatic Standby Generator ASPAS1BBA007 User Manual

Page 9

Advertising
background image

9. Reverse procedure steps 1-5 to reinstall demand

regulator.

10. Reverse the procedure to convert back to natural

gas.

1.7.2

12KW AND 15KW, V-TWIN ENGINES

To reconfigure the fuel system from NG to LP,

follow these steps:

NOTE:

The primary regulator for the propane supply is NOT

INCLUDED with the generator. A fuel pressure of 11

to 14 inches of water column (0.4 to 0.5 psi) to the

fuel inlet of the generator MUST BE SUPPLIED.
1. Turn off the gas supply. (if connected)
2. Open the top and remove the front panel.
3. Remove the battery. (if installed)
4. Remove the engine air in baffle located on the left-

hand side of the battery compartment. Two M6

screws are located on top of the baffle and two M6

screws are located on the inside of the baffle towards

the back.

5. Remove the small hose clamp and hose from the fuel

regulator. It may be necessary to pry the hose off of

the brass fitting using a screwdriver to gently lift up

the hose edge.

6. Remove the small brass hose fitting from the

regulator casting.

7. Place the small fuel jet, thread side first, into the

threaded hole originally occupied by the brass hose

fitting (Figure 1.4).

8. Using a short No. 2 Phillips screw driver, thread the

small fuel jet into the regulator casting. Do not over

tighten.

9. Apply thread sealant to the threads of the hose fitting

and replace it into the regulator body.

10. Re-attach the small hose and hose clamp and tighten

as necessary.

11. Replace the engine air in baffle using the four M6

screws.

12. Identify both brass adjustment screws on the

regulator.

NOTE:

One adjustment screw can be accessed from the

front of the unit and the second can be accessed

from the back of the unit enclosure by removing the

plastic hole plug. The screw can be turned with a

long flat blade screwdriver.
13. To adjust the system to run on LP fuel, turn BOTH

adjuster screws 1/2 TURN CLOCKWISE. The

system should now be set for maximum power and

best performance. DO NOT, UNDER ANY

CIRCUMSTANCES, REMOVE THE SET PINS

FROM THE REGULATOR HOUSING. THIS WILL

VOID THE WARRANTY.

14. It may be necessary to make minor adjustments to

the preset adjustment screw settings to achieve

maximum power, particularly at higher altitudes. If

experiencing problems with the unit producing

maximum power, follow the procedure in Section 1.6

(Adjusting the Fuel Regulator).

Figure 1.4 - Demand Regulator

1.8

ENGINE GOVERNOR ADJUSTMENT

If both AC frequency and voltage are correspondingly

high or low, adjust the engine governor as follows:

1.8.1 7 KW UNITS

1. Loosen the governor clamp bolt (Figures 1.5).
2. Hold the governor lever at its wide open throttle

position, and rotate the governor shaft clockwise as

far as it will go. Then, tighten the governor lever

clamp bolt to 70 inch-pounds (8 N-m).

3. Start the generator; let it stabilize and warm up at no-

load.

4. Connect a frequency meter (or high quality multi-

meter set to the frequency mode) across the

generators AC output leads.

5. Turn the speed adjust nut to obtain a frequency

reading of 63 Hertz.

Figure 1.5 — Engine Governor Adjustment

Single Cylinder Engines

BRASS HOSE

FITTING

IDLE CIRCUIT

PORT

U

1

T

TAP

1/8 NPT

BRASS HOSE
FITTING

FUEL HOSE

SMALL
FUEL JET

REGULATOR
HOUSING PORT

ADJUSTER
SCREWS

OUTLET PORTS

GOVERNOR

SHAFT

ADJUST

SCREW

GOVERNOR

CLAMP

BOLT

Section 1 — Post Installation Start-up and Adjustments

Bryant Air-cooled 7 kW, 12 kW and 15 kW Generators

Bryant

7

Advertising