Bryant DURAPAC 579F User Manual

Page 37

Advertising
background image

37

LEGEND AND NOTES FOR FIG. 46 AND 47

QT

Quadruple Terminal

RAT

Return Air Temperature Sensor

RS

Rollout Switch

SN

Sensor

SW

Switch

TB

Terminal Block

TC

Thermostat Cooling

TH

Thermostat Heating

TRAN — Transformer

Terminal (Marked)

Terminal (Unmarked)

Terminal Block

Splice

Factory Wiring

Field Wiring

Option/Accessory Wiring
To indicate common potential only;
not to represent wiring.

Economizer Motor

Remote POT Field Accessory

OAT Sensor

Disch Air Sensor

RAT Accessory Sensor

Low Ambient Lockout Switch

AHA

Adjustable, Heat Anticipator

BRK W/AT — Breaks With Amp Turns
C

Contactor, Compressor

CAP

Capacitor

CB

Circuit Breaker

CC

Cooling Compensator

CLO

Compressor Lockout

COMP

Compressor Motor

CTD

Compressor Time Delay

DM

Damper Motor

DU

Dummy Terminal

EQUIP

Equipment

FU

Fuse

GND

Ground

HPS

High-Pressure Switch

IAQ

Indoor Air Quality Sensor

IDM

Induced Draft Motor

IFC

Indoor-Fan Contactor

IFM

Indoor-Fan Motor

IFR

Indoor Fan Relay

IGC

Integrated Gas Unit Controller

L

Light

LALS

Low Ambient Temperature

Compressor Lockout Switch

LPS

Low-Pressure Switch

LS

Limit Switch

MGV

Main Gas Valve

NEC

National Electrical Code

OAT

Outdoor Air Temperature Sensor

OCCUP

Occupancy Sensor

OFC

Outdoor Fan Contactor

OFM

Outdoor Fan Motor

PL

Plug Assembly

PMR

Phase Monitor Relay

LEGEND

NOTES:

1. Compressor and/or fan motors thermally protected; three phase motors protected against primary single-

phasing conditions.

2. If any of the original wire furnished must be replaced, it must be replaced with type 90 C wire or its equiv-

alent.

3. TRAN1 is wired for 230-v operation. If unit is 208-v, disconnect the BLK wires from the ORN TRAN wire

and reconnect to the RED TRAN wire. Apply wirenuts to wires.

4. CB1, 2 Must Trip Amps are equal to or less than 156% FLA, IFCB 140%.
5. The CLO locks out the compressor to prevent short cycling on compressor overload and safety devices.

Before replacing CLO, check these devices.

6. Jumpers are omitted when unit is equipped with economizer.
7. Number(s) indicates the line location of used contacts. A bracket over (2) numbers signifies a single-pole,

double-throw contact. An underlined number signifies a normally closed contact. A plain (no line) number
signifies a normally open contact.

8. Remove jumper between RC & RH.
9. 620 Ohm, 1 watt, 5% resistor should be removed only when using differential enthalpy or dry bulb.

10. If a separate field-supplied 24-v transformer is used for the IAQ sensor power supply, it cannot have the

secondary of the transformer grounded.

11. OAT sensor is shipped inside unit and must be relocated in the field for proper operation.
12. For field-installed remote minimum position POT, remove black wire jumper between P and P1 and set

control minimum position POT to the minimum position.

Advertising