Specifi cations

Input fi ring range 300 to 1200 MBh

Fuel Natural gas - 0.6 specifi c gravity typical

Gas train Standard: UL listed/CSD-1 Confi guration

Options: IRI and FM

Manifold pressure 1.0 to 4.6 inches W.C. typical

Firing mode On/Off or On/Off with Low Fire Start

Flame safeguard RM7895A Standard (Options available)

Flame detection Standard: Flame rod rectifi cation

Optional: Ultraviolet scanner

Air proving switch Standard

Gas pressure

switches

Standard high and low

Ignition Direct spark main fl ame

Motor Standard: 1/3 HP; 3450 RPM; 120 volt/60 hz,

single phase
Optional motor: 50 or 60 hz (see notice for 50
hz), 240 volt single phase

Weight 55 lbs.

Features

S - Standard O - Optional N/A - Not Available

On/Off with Low Fire Start

S

Propane Restrictor

O

Linkageless Low/High/Low or Low/High/Off

N/A

Modulation with Pressure/Temperature Modulating Controller

N/A

Right or Left Side Gas Train Connection

S

Air Pressure Switch

S

Low Gas Pressure Switch

S

High Gas Pressure Switch

S

Main Shutoff Cock, Leak Test Cock, Test Connections, and Test Cocks

S

Direct Spark Ignition of Main Flame

S

Flame Safeguard with Flame Rod

O

Flame Safeguard with UV Sensor

S

Customized Electrical Cabinet

O

UL/CUL - CSD1 - Swiss Re

S

FM

O

IRI (old standard)

O

Power On - Fuel On, Indicator Light

O

11.7

6.0

8.1

4.4

4.6

25.5

6.8

8.2

9.9-11.0

Overall Dimensions

Gas Gun Assembly

BECKETT

CG10

COMMERCIAL GAS BURNER

Gas Train Assembly (Typical Gas Train, other confi gurations are available)

LGPS

TC

TC

HGPS

MSC

U

SSOV1

2PRSSOV

MLTC

U

TP