DS240/DS241 Installation Instructions

6.0

WIRING

Only apply power after all connections have been made
and inspected.

• Wire the transmitter and receiver terminals as follows (see

Figure 6).

NOTE: Do not install on verified fire circuits.

Figure 6 - Wiring a Single Unit

NOTE: Do not coil excess wiring inside the units.

Transmitter Terminals 1 & 2:

Input power terminals. See

Section 2.0 Specifications on page 1

for the operating voltages of the DS240 and DS241.

Receiver Terminals 1, 2 & 3:

Form "C" Auxiliary relay contacts. Terminals 1 & 2 will open on fire
alarm; Terminals 2 & 3 will close (short) on fire alarm.

Receiver Terminals 4 & 5:

Normally Open Fire alarm contacts will close (short) on fire
alarm.

Receiver Terminals 6 & 7:

Normally Closed Trouble contacts will open for trouble alarm.

Receiver Terminals 8 & 9:

Input power terminals. See

Section 2.0 Specifications on page 1

for the operating voltages of the DS240 and DS241.

NOTE: Resetting from a fire alarm requires power to the receiver to

be interrupted for at least one second. If not provided by the
fire panel, it can be accomplished by installing a switch in
series with Terminal 9.

Remote Indicator Plate
The DIS2000 Remote Indicator Plate is shipped with the DS240/
DS241 as a standard accessory. Although the Remote Indicator Plate
is not required, the manufacturer recommends its installation to
provide a means of checking the condition of the detector from ground
level.

If a DIS2000 or DIS240 Remote Indicator Plate will be used, install
the Remote Indicator Connector to the receiver now (see Figure 7).

NOTE: The DIS240 remote indicator should be located no further

than 100 ft (31 m) from the receiver and wired with 18 AWG
(1.2 mm) or larger wire. The DIS2000 may be wired up to
500 ft (152 m) from the receiver.

• Slide the Remote Indicator Connector over the pins just to the

right of the receiver’s terminal strip.

Figure 7 - Connecting the DIS2000 Remote Indicator Plate

NOTE: If connecting a DIS240 Remote Test/Indicator Plate,

consult the

DIS240 Installation Instructions (P/N: 24171).

7.0

SET-UP

Before starting this section, confirm that all connections have been
made and are secure, then apply power to both units.

• Press the Aim Mode button (directly above the green LED) on the

transmitter (see

Figure 8). This allows the transmitter to power

up while its cover is off.

AIM MODE

BUTTON

GREEN

LED

Figure 8 - Cutout View of Transmitter Circuit Board Showing

Aim Mode Button Location

- Check the transmitter’s green LED. It should be flashing on

and off.

CAUTION

Alarm Loop

Power Loop +

Power Loop –

Fire Alarm

Control Panel

DS240/DS241 Receiver

9

8

7

6

5

4

Fire

Alarm

Trouble

Alarm

+

10 to 32

VDC

EOL

Voltage Monitor

Ground (–)

Red LED

Green LED

Yellow LED

DIS2000

Violet

Black

Red

Yellow

Green

Remote Indicator

Plate Connector

1

2

3

4

5

6

7

AUX.

RELAY

ALARM

FIRE

ALARM

TRBL

ALARM

8

9

+

VDC

Receiver

1

2

+

Transmitter

End of Line

resistor

Alarm Loop

Power Loop –
Power Loop +

Fire Alarm

Control Panel

Advertising
This manual is related to the following products: