Objects 1-16 – Zone Objects

There is one Zone Object for each sampling zone in the HGM300 (16 total):



Network output variable nvoHgmZonePPM shows the measured gas concentration for
a particular zone. The value will range from 0-65535 PPM.

Network output variable nvoHgmZoneStatus is a text string that displays information
about the zone status and the refrigerant type being sensed.

Possible Zone Status values:

ZONE NORMAL
No alarms, no faults, HGM in normal operating mode.
LEAK ALARM
Leak alarm active for this zone.
SPILL ALARM
Spill alarm active for this zone.
EVAC ALARM
Evacuate alarm active for this zone.
ACKD LEAK ALM
Acknowledged Leak alarm active for this zone.
ACKD SPILL ALM
Acknowledged Spill alarm active for this zone.
ACKD EVAC ALM
Acknowledged Evacuate alarm active for this zone.
ZONE FLOW FAULT
This zone has a flow fault (other zones not affected).