5

Table 2 – Rating Plate (required) Subcooling Temperatures

Measure

Liquid Pressure

(psig)

R---410A Required Liquid Line Temperature _F (_C)

_

F

(_C)

_

F

(_C)

_

F

(_C)

_

F

(_C)

_

F

(_C)

_

F

(_C)

6

3

8

4

10

6

12

7

14

8

16

9

251

78

26

76

24

74

23

72

22

70

21

68

20

259

80

27

78

26

76

24

74

23

72

22

70

21

266

82

28

80

27

78

26

76

24

74

23

72

22

274

84

29

82

28

80

27

78

26

76

24

74

23

283

86

30

84

29

82

28

80

27

78

26

76

24

291

88

31

86

30

84

29

82

28

80

27

78

26

299

90

32

88

31

86

30

84

29

82

28

80

27

308

92

33

90

32

88

31

86

30

84

29

82

28

317

94

34

92

33

90

32

88

31

86

30

84

29

326

96

36

94

34

92

33

90

32

88

31

86

30

335

98

37

96

36

94

34

92

33

90

32

88

31

345

100

38

98

37

96

36

94

34

92

33

90

32

364

104

40

102

39

100

38

98

37

96

36

94

34

374

106

41

104

40

102

39

100

38

98

37

96

36

384

108

42

106

41

104

40

102

39

100

38

98

37

395

110

43

108

42

106

41

104

40

102

39

100

38

406

112

44

110

43

108

42

106

41

104

40

102

39

416

114

46

112

44

110

43

108

42

106

41

104

40

427

116

47

114

46

112

44

110

43

108

42

106

41

439

118

48

116

47

114

46

112

44

110

43

108

42

450

120

49

118

48

116

47

114

46

112

44

110

43

462

122

50

120

49

118

48

116

47

114

46

112

44

474

124

51

122

50

120

49

118

48

116

47

114

46

Table 3 – Superheat Charging -- AC Only

OUTDOOR TEMP (_F)

EVAPORATOR ENTERING AIR TEMPERATURE (_F WB)

50

52

54

56

58

60

62

64

67

68

70

72

74

76

55

9

12

14

17

20

23

26

29

32

35

37

40

42

45

60

7

10

12

15

18

21

24

27

30

33

35

38

40

43

65

6

10

13

16

19

21

24

27

30

33

36

38

41

70

7

10

13

16

19

21

24

27

30

33

36

39

75

6

9

12

15

18

21

24

28

31

34

37

80

5

8

12

15

18

21

25

28

31

35

85

8

11

15

19

22

26

30

33

90

5

9

13

16

20

24

27

31

95

6

10

14

18

22

25

29

100

8

12

15

20

23

27

105

5

9

13

17

22

26

110

6

11

15

20

25

115

8

14

18

23

*Optimum performance point, 95_F (35_C) outdoor ambient and (80_F / 27_C dry bulb), (67_F / 19_C wet bulb) indoor conditions. (DOE A Test Conditions)

Where a dash (--- --- ) appears do not attempt to charge system under these conditions or refrigerant slugging may occur. Charge must be weighed in.

Note: Superheat _F is at low---side service port, Allow a tolerance of ±3_F (±1.7_C)

Note: Indoor dry bulb between 70_F and 80_F (21_C and 27_C)

113A