• Burner shall be equipped with a burner-mounted 12 x 16 control panel consisting of all required

operating electrical components. All wiring within the panel shall be factory prewired to a terminal strip.
The panel shall have an illuminated rocker switch that will limit the burner to its low fire rate for set-up
adjustments. The control panel shall be furnished with the following:

o Power On Light/Switch
o Fuel On Light
o 120V Alarm (24V alarm)
o Flame Fail Light
o Low Water Cutoff Light
o High Limit Light
o Call for Heat Light
o Ignition Light
o Control Transformer

• Burner shall be equipped with a 12 x 16 remote control panel consisting of all required operating

electrical components. All wiring within the panel shall be factory prewired to a terminal strip. A
junction box pre-wired to the burner components shall be mounted on the burner. It shall have a terminal
strip which will match a terminal strip in the remote panel. Field wiring will be required between the
burner mounted junction box and the remote panel. The panel shall have an illuminated rocker switch
that will limit the burner to its low fire rate for set-up adjustments. The control panel shall be furnished
with the following:

o Power On Light/Switch
o Fuel On Light
o 120V Alarm (24V alarm)
o Flame Fail Light
o Low Water Cutoff Light
o High Limit Light
o Call for Heat Light
o Ignition Light
o Control Transformer




Product Liability Insurance:

The burner manufacturer will provide an insurance certificate documenting his current coverage of Product
Liability Insurance with minimum coverage of $10,000,000.

Burner Start up Information and Test Data:

On completion of the burner system start up- the installing contractor will complete the attached “Burner Start
Up and Test Data” form and deliver to

the

Specifying

Engineer.