Bryant 580J***(D User Manual

Submittal data, 580j***(d,f), Description

Advertising
background image

580J***(D,F)

SINGLE PACKAGE ROOFTOP

GAS HEATING/ELECTRIC COOLING UNIT

TWO STAGE COOLING CAPACITY CONTROL WITH NOVATIONt COIL

SIZES 08, 12, 14 WITH PURONR (R--410A) REFRIGERANT

Submittal Data

®

This product has been designed and manufactured

to meet Energy Star® criteria for energy efficiency.

However, proper refrigerant charge and proper air

flow are critical to achieve rated capacity and effi-

ciency. Installation of this product should follow all

manufacturer’s refrigerant charging and air flow in-

structions.

Failure to confirm proper charge and

air flow may reduce energy efficiency and short-

en equipment life.

DESCRIPTION

580J***(D,F) units are high--efficiency, single--packaged

electric cooling, gas heating units that are pre--wired and

pre--charged with PuronR (R--410A) HFC refrigerant.

Units utilize an all aluminum flat micro--channel tube

with louvered fins condenser coil—NOVATIONt. The

units are factory tested in both heating and cooling modes.

These units meet the ASHRAE 90.1--2007 and Energy

Star minimum efficiency levels as well as also meeting

2010 efficiency standards.

STANDARD FEATURES

Base Unit

S

Puron (R--410A) HFC refrigerant

S

ARI certified efficiency levels up to 11.1 EER

S

Rated in accordance with ARI Standard 360

S

Designed in accordance with Underwriters’ Laboratories Std
1995 and listed by UL and UL, Canada

S

Two--stage cooling capacity control

S

Non--corrosive composite sloping design; side or center drain
condensate pan. Meets ASHRAE Standard 62

S

Standard cooling operating range from 40_F up to 115_F
(4_C up to 46_C). Field installable accessory extends the
minimum down to --20_F (--29_C).

S

Convertible from vertical to horizontal airflow for slab mounting

S

Two--inch disposable return air filters

S

Thru--the--bottom power and gas entry capability

S

Single point gas and electric connections

S

24--volt control circuit protected with resettable circuit breaker
and 75--VA transformer

S

Belt drive, constant torque, permanently lubricated
evaporator–fan motor

S

Totally enclosed condenser motors with permanently lubricated
bearings

S

Low--pressure and high--pressure switches

S

Full perimeter base rail with built--in rigging adapters and fork
truck slots

S

Centralized Terminal Board for component and unit wiring
connections

Cabinet

S

Access panels with easy grip handles and NO--STRIP screw
collar

S

Pre--painted exterior panels and primer--coated interior panels
tested to 500 hours salt spray protection

S

Fully insulated cabinet

S

Tool--less filter access door

Refrigerant System

S

Acutrolt refrigerant metering system

S

Liquid line filter drier

S

Scroll compressors with internal line--break overload protection

S

Copper

tube

, aluminum fin evaporator coil

S

NOVATION all aluminum condenser coil

S

Removable gauge line plugs for reading refrigerant pressure
with unit panels in place

Gas Heat

S

IGC solid--state gas heat exchanger control for on--board
diagnostics, anti--cycle protection, LED error code designation,
burner control logic and energy saving indoor fan motor delay

S

Gas efficiencies up to 82%

S

Designed in accordance with ANSI Z21.47 (design and test
standard for gas furnaces) and ANSI Z233.1 (National Fuel Gas
code relating to appliance installation requirements)

S

Induced draft combustion

S

Redundant gas valve, with up to 2 stages of heating

S

Flame roll--out safety protector

S

Solid--state electronic direct spark ignition system

Advertising