3

cross-sectional area should be at least equal to the sum of

the individual vent areas.

The outside end of the vent line should either have a weather-

proof vent cap or should be directed downward for weather

protection. It should also be screened to prevent foreign ma-

terial or insects from entering the line. Naturally, the end of

the line should be located in an area where it is safe to re-

lease gas.

A high percentage of regulator problems is due to improper

venting. Remember the space over the diaphragm must be

able to breathe for proper regulation. If there is any regulation

problem, disconnect the vent line at the regulator to see if

proper venting is the solution. Then look for undersized lines,

crimped tubing, clogged lines, back pressure caused by draft

effect at end of vent or pressure effect from other regulators in

a grouped system.

VI.

INSTA L L ATION (ELECTRICAL)

All internal electric wiring is factory installed. It is only neces-

sary to connect main power leads to terminals LI - L2 - L3 of

the tenminal strip inside the cabinet, and to wire between re-

mote station, doorswitch, and heater.

The remote station may be installed at any location for conve-

nience in switching the heater to “OFF” or “SUM” for warm

weather.

The door limit switch must be installed on the door frame in

such a way that it is tripped by the opening of the door.

A

switch having 2 poles, one normally open and one normally

closed, is furnished, so that whichever pole is closed by the

opening of the door, may be used to actuate the heater.

VII.

INSTA L L ATION (GAS PIPING)

(See Section Mounting Position Plumbing)

CAUTION: When making up gas piping, be sure all valves are

in a horizontal portion of the gas line, with valve body properly

positioned:

(A) Main safety valve actuator may be in any position.

(B) Pilot gas valve mounts in any position except with

solenoid inverted (vertically down).

(C) Secondary safety valve must have the solenoid up-

right, no more than 5º out of plumb, in a horizontal gas

line.

(D) Vent valve may be mounted in any position.

(E) Regulator may be removed and reinstalled further

upstream in the gas line, but no further than a few feet

from the heater. Regulators may be installed in any posi-

tion, except do not install a Maxitrol low pressure regula-

tor in a vertical-up gas line.

A manual cock (not furnished) should be piped in ahead of the

regulator. (See schematic piping on wiring diagram.)

VIII.

SAFETY DEVICES

(A) Gas Pressure Switches*: Two U.L. listed gas pres-

sure supervising switches are used, to shut off gas if pres-

sure falls below or rises above the proper operating range.

(See wiring diagram for proper setting.) Switches are pre-

set at the factory during checkout.

Both switches have a vent connection for venting gas in case

of a ruptured diaphragm. Connect vent to atmosphere per

(Suggestions for Regulator Venting) above. The switches lock

out if tripped, and must be manually reset. Thus, whenever

gas is turned off manually, 1PS must be reset.

(B) Safety Shut-Off Valve: This heater is equipped with

a motor operated gas valve having closing spring that ex-

erts a force in excess of 5 lbs. It is a fast-open, instant

close valve meeting the requirements of FM, UL, AGA

and CSA.

(C) Hi-Temperature Limit: The “Thermodisc” limit switch

is located near the discharge end of the heater, mounted

on the top outside of the duct. This is a U.L. approved

manual-reset device.

(D) Airflow Switch: A UL-FM approved differential pres-

sure switch in the control cabinet senses velocity plus

s

tatic pressure of the airflow from the propeller.

This air pressure closes the switch contact to power the

gas system, thus assuring that the fan is on before the

gas can ignite.

(E) Gas Control: The flame safeguard is Fireye UVM- 1

F, which utilizes a flame scanner with an ultraviolet-sensi-

tive gas discharge tube to monitor visually both pilot and

main flame. At any time that it senses no flame, it de-

energizes the automatic gas valve. (UL-FM approved)

With this unit, if main burner goes off after ignition, or if pilot

fails to ignite at startup after an approximate 5-second trial-

for-ignition, an external relay (CR) de-energizes the flame safe-

guard (CRE), and lights the small green “TURN RESET” pilot

light. If this happens, turn the remote selector to “OFF/RE-

SET” then back to “WIN” to reset CR for another start. Re-

peated failure to ignite may result in lockout of the CRE flame

safeguard itself, causing small red “LOCKOUT” pilot to light.

This button must then be reset at the control cabinet before

another try-for-ignition can be made. If electric power to the

control circuit fails for any reason, whether intentional or oth-

erwise, and no matter how briefly, the flame safeguard gives a

safe-start component check when power is restored. If a flame

simulating component failure exists it will not proceed to the

ignition cycle and will not energize the main gas valve.

The flame safeguard senses first the presence of pilot flame.

Then, after the main automatic valve opens, the pilot is inter-

rupted and main flame only is monitored. If main flame fails

after pilot is interrupted there will be a 5 second trial for re-

ignition per 2nd preceding paragraph.